期刊文献+

一起低压综合配电箱短路事故的分析

Analysis of a Short-Circuit Accident for Low-Voltage Integrated Distribution Box
下载PDF
导出
摘要 针对一起低压综合配电箱投入运行时发生的短路事故,对该事故进行了理论分析、计算和现场验证,发现是因加工切屑在断路器投运震动时移位造成短路事故,且由于未在断路器的进线端铜排之间安装隔弧板从而导致事故扩大,并从生产制造、安装前检查、安装后须进行绝缘测试等方面提出了预防措施。 Aiming at a short-circuit accident happened during low-voltage integrated distribution box running, this paper analyzed the accident theoretically and carried out calculation and onsite examine, fi nding that when the process chipping, the shift of circuit breakers running shaking caused the short-circuit accident. Because there was non anti-arc board installed between copper bars of inlet wire end of circuit breakers, the accident enlarged. This paper proposed some preventive measures from the aspects of production manufacturing, examine before installation, insulation testing after installation etc.
作者 朱遵义 王瑞
出处 《电工电气》 2014年第12期42-44,共3页 Electrotechnics Electric
关键词 低压综合配电箱 短路事故 电弧 low-voltage integrated distribution box short-circuit accident electric arc
  • 相关文献

参考文献2

二级参考文献2

共引文献9

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部