电泵联锁启动过程中快切动作分析及处理 被引量:1

Analysis and treatment of fast change-over during pump interlocked startup
下载PDF
导出
摘要 对某厂3号机组发生的3次跳机事故中的快切动作过程进行了分析,通过分析及试验论证了电泵联锁启动过程中发生快切引起6 k V母线电压降低,从而导致400 V电压降低、400 V辅机控制回路交流接触器返回后辅机跳闸的原因,并提出了相应的处理方法。 This paper analyzes strates the reasons, through the process of fast change -over the analysis and experiment, why in three trip accidents in No. 3 unit, and demon- fast change -over happening during pump inter- locked startup lowers the 6 kV bus bar voltage, accordingly causing 400 V voltage reduction and auxiliary trip after the return of 400V ac contaetor auxiliary control loop, and proposes relevant countermeasures.
出处 《黑龙江电力》 CAS 2014年第6期557-560,564,共5页 Heilongjiang Electric Power
关键词 快切 电泵 残压 交流接触器 辅机跳闸 fast change- over pump residual voltage alternating current contactor auxiliary trip
  • 相关文献

参考文献8

二级参考文献19

  • 1潘飞.电动机再起动技术[J].电工技术杂志,2004,26(3):19-23. 被引量:13
  • 2马宏忠,胡虔生,张利民,韩敬东.异步电机的失电残余电压研究[J].中小型电机,2005,32(5):3-5. 被引量:18
  • 3汤蕴Qiu.电机学[M].北京:机械工业出版社,1999..
  • 4商景德 王祥珩 等.交流电机及其系统分析[M].北京清华大学出版社,1992..
  • 5张麟征.异步电机的暂态分析及其应用[J].电机与控制学报,1997,1(1):18-21. 被引量:6
  • 6团体著者,达拉特发电厂厂用电动机群动态仿真计算研究报告,1996年
  • 7黄纯华,电工技术学报,1990年,4期
  • 8DAS J C. Effects of momentary voltage dips on the operation of induction and synchonous motors [J]. IEEE Trans. on Industry Applications, 1990,26(4) :711-718.
  • 9PILLAY P. Reclosing transient in induction machines including the effects of saturation of the mag netizing branch and a pratical case study[J]. IEEE Trans. on Energy Conversion, 1994,9(2) :383-389.
  • 10HALLENIUS K E,VAS P,BROWN J E. The analysis of a saturated self-excited asynchronous generator[J]. IEEE Trans. on Energy Conversion, 1991 (2) :336-341.