三相逆变器新型积分控制加状态反馈控制 被引量:1

Novel state-feedback and integral control strategy for three-phase inverter
下载PDF
导出
摘要 三相逆变器在实际运行中,不平衡负载工况较为常见,原因是传统积分控制加状态反馈控制无法实现三相输出电压的对称性。针对该问题提出了不平衡负载条件下三相逆变器新型积分控制加状态反馈控制策略,并通过仿真和实验验证了该策略能有效降低不平衡负载时三相逆变器输出电压的不平衡度,从而获得对称的三相输出电压波形。 The unbalance load is very common in the three-phase inverter system. As the traditional state-feedback and integral control strategy can not meet the symmetry of voltage output, a novel state-feedback and integral control technique is proposed. The simulative and experimental results verify that this strategy can effectively reduce the output voltage unbalance caused by the unbalanced load, thereby obtaining high-quality voltage waveforms of the three-phase inverter system.
出处 《海军工程大学学报》 CAS 北大核心 2014年第6期6-11,共6页 Journal of Naval University of Engineering
基金 国家重点基础研究发展计划资助项目(2012CB215103 2013CB035601) 新世纪优秀人才支持计划资助项目(NECT-11-0871)
关键词 三相逆变器 不平衡负载 电压对称性 信号延迟对消技术 three-phase inverter unbalanced load voltage symmetry DSC (delay signal cancella tion)
  • 相关文献

参考文献10

  • 1曹太强,祁强,王军.三相逆变电源不平衡负载控制方法的研究[J].电机与控制学报,2012,16(4):50-55. 被引量:26
  • 2KESLER M, OZDEMIR E. Synchronous reference frame based control method for UPQC under un- balanced and distorted load conditions [J]. IEEE Transations on Industrial Electronics, 2011, 58(9):3967-3975.
  • 3王恒利,付立军,肖飞,揭贵生,朱威.三相逆变器不平衡负载条件下双环控制策略[J].电网技术,2013,37(2):398-404. 被引量:70
  • 4PATTNAIK M,KASTHA D. Unbalance and har- monic voltage compensation for a stand-alone varia- ble speed constant frequency double-output induc- tion generator supplying non-linear and unbalanced loads [J]. Electric Power Applications, IET, 2013,7(1) :27-38.
  • 5BORSALANI J, DASTFAN A. Decoupled phase voltages control of three phase four-leg voltage source inverter via state feedback [C]// Interna- tional Conference on Computer and Knowledge En-gineering (ICCKE). Mashhad, Iran.. IEEE, 2012.
  • 6DEHGHAN S M, AHMAD A A, LOURAKZA- DEGAN R, et al. A high performance controller for parallel operation of three-phase UPSs powe- ring unbalanced and nonlinear loads [C]~//Power Electronics, Drive Systems and Technologies Con- ference (PEDSTC). Tehran, Iran.- IEEE, 2011.
  • 7ATSUSHI T, ITSUO Y, TSUYOSHI O. The control method of 3-phase PWM converter for 3- phase 3-wired imbalanced AC voltages [C]~//Tele- communications Energy Conference (INTELEC). Amsterdam, Holland: IEEE, 2011.
  • 8ASADI M, JALILIAN A, FARAHANI H F. Compensation of unbalanced nonlinear load and neutral currents using stationary reference frame in shunt active filters [C]/ International Conference on Harmonics and Quality of Power (ICHQP). Bergamo, Italy.. IEEE, 2010.
  • 9王恒利,付立军,揭贵生,肖飞.并网逆变器积分控制加状态反馈数字控制研究[J].电力电子技术,2013,47(6):7-9. 被引量:1
  • 10ZAREI M E, ASAEI B. Combined vector control and direct power control methods for DFIG under normal and unbalanced and distorted grid voltage conditions [C~]//Power Electronics, Drive Systems and Technologies Conference (PEDSTC). Tehran, Iran: IEEE, 2013.

二级参考文献34

  • 1孙驰,马伟明,鲁军勇.三相逆变器输出电压不平衡的产生机理分析及其矫正[J].中国电机工程学报,2006,26(21):57-64. 被引量:62
  • 2伏祥运,王建赜,张小聪,曾繁鹏,纪延超.三相电压源型逆变器级联的静止同步补偿器[J].电网技术,2006,30(22):72-76. 被引量:19
  • 3ROY S, UMANAND L. Control technique for non-linear and un- balance compensation of an integrated magnetics-based three-phase series-shunt-compensated uninterruptible power supply [ J]. IET Power Electronics,2012,5 ( 1 ) : 95 - 105.
  • 4KUANG L, JINJUN L, ZHAOAN W, et al. Strategies and operat- ing point optimization of statcom control for voltage unbalance miti- gation in three-phase three-wire systems [ J ]. IEEE Transactions on Power Delivery, 2007,22( 1 ) :413 -422.
  • 5JENSEN U B, ENJETI P N, BLAABJERG F. A new space vector based control method for ups systems powering nonlinear and un- balanced loads [ M ]. ISBN : 0 - 7803 - 5864 - 3, 2000.
  • 6SANCHIS P, URSUA A, GUBIA E, et al. Control of three-phase stand-alone photovoltaic systems with unbalanced loads [J]. IEEE ISIE, 2005, 20(23) : 633 -638.
  • 7KYUNG Hwan K, NAM Joo P, DONG Seok H. Advanced syn- chronous reference frame controller for three-phase UPS powering unbalanced and nonlinear laods[ C ]. IEEE 36th Power Electronics Specialists Conference, 2005, PESC'05, June 16, 2005, Recife, Brazil. 2005 : 1699 - 1704.
  • 8FRANCISCO D, ALEJANDRO G. Three-phase plls with fast post- fault retracking and steady-state rejection of voltage unbalance and harmonics by means of lead compensation[ J ]. IEEE Transactions on Power Electronics, 2011,26 ( 1 ) : 85 - 97.
  • 9MAKBUL A, AYONG H. New unbalance factor for estimating per- formance of a three-phase induction motor with under-and overvolt- age unbalance [ J ]. IEEE Transactions on Energy Conversion, 2010, 25(3) :619 -625.
  • 10MARTINEZ V L, ROMEU J M, GARCIA J M P. Unbalance compensator for three-phase industrial installations [ J ]. IEEE Latin America Transactions, 2011,9(5) :808 -814.