期刊文献+

温和地区采用大温差空调系统的技术经济分析

Technical and Economic Analysis of Air-conditioning Water System Using Large Temperature Difference in Temperate Regions
下载PDF
导出
摘要 在温和地区的气候条件下和特定的使用功能要求下,分析比较了空调水系统采用大温差和常规温差对于风机盘管﹑新风和空气处理机组﹑冷水机组﹑冷冻冷却水泵﹑冷却塔﹑空调热水泵等设备运行工况的影响,认为对本项目最适宜的选择是空调冷水5∽12℃、热水60∽45℃,冷却水28∽36℃。 Under the climatic condition of temperate regions and the requirement of specific use, The effect of using large temperature difference and conventional temperature difference in air conditioning water system on the operating conditions of fan coil, fresh air and air handling units, water chiller, cooling tower, chilled water pump, cooling water pump and air conditioning heat pump and other equipments were analyzed and compared. It is considered that the optimum temperature difference is 5∽12℃for air conditioning cold water, 60∽45℃for heat water and 28∽36℃for Cooling water, respectively.
作者 段灼伟
出处 《制冷与空调(四川)》 2014年第6期672-676,共5页 Refrigeration and Air Conditioning
关键词 温和地区 大温差 技术经济分析 Temperate regions Large temperature difference Technical and economic analysis
  • 相关文献

参考文献4

  • 1GB50736-2012,民用建筑供暖通风与空气调节设计规范[S].北京:中国建筑工业出版社.2012.
  • 2GB50189-2005,公共建筑节能设计标准[S].北京:中国建筑工业出版社,2005.
  • 3住房和城乡建设部工程质量安全监管司,中国建筑标准设计研究院.全国民用建筑工程设计技术措施·节能专篇:暖通空调·动力[M].北京:中国计划出版社,2007.
  • 4DBJ53/T-39-2011,云南省民用建筑节能设计标准[s].云南:云南科技出版社,2012.

共引文献40