期刊文献+

侧向排烟口对双层隧道机械排烟的影响 被引量:12

Influence of lateral smoke vent on mechanical smoke exhaust in double-decked tunnel
下载PDF
导出
摘要 双层隧道具有空间利用率高,通行量大等优点,但由于顶部空间有限,多采用侧向排烟的方式控制隧道火灾时烟气的蔓延。以某越江隧道为例,采用火灾动态模拟软件FDS,改变排烟口数量、面积、间距,设计6个火灾场景,定量分析侧向排烟口的设置对机械排烟效果的影响。分析各排烟口流量、流速,分析隧道内温度分布、能见度分布。结果表明:在火源功率20 MW、无纵向风条件下,排烟口面积、排烟口开启数量以及排烟口间距都在火灾发生初期对烟气的蔓延起控制作用;提出在排烟口面积为4m2、排烟口间距为90m、火灾时开启4个排烟口时,排烟效果更经济合理。 Double-decked tunnels with the high space utilization and big traffic flow, was limited by the space on the top, so it usually choose the lateral pattern to control tunnel fire smoke spread. With the example of a tunnel through the river, setting 6 scenarios by varying the number and area and distance of smoke vent, FDS was adopted to analyze the influence of the lateral ventilation on the mechanical smoke exhaust quantitatively. The quantity and speed of flow at the vent, the distribu- tion of temperature and visibility in tunnel, were obtained. The paper proposed that the area, number and the distance of smoke vent can obviously impact the spread of fire smoke only in the early of the fire in the conditions of the fire power of 20 MW and no longitudinal wind; The design with the parameters as the smoke vent area of 4 m^2 , the distance of 90 m, and opening 4 smoke vents when fire, is more reasonable and economic.
出处 《消防科学与技术》 CAS 北大核心 2015年第1期33-37,共5页 Fire Science and Technology
基金 国家自然科学基金项目(51204123) 武汉地铁集团有限公司科研项目(GS-JZ-229 GS-JZ-230)
关键词 双层隧道 侧向排烟口 机械排烟 排烟效率 排烟口间距 能见度 double-decked tunnel lateral smoke vent mechani-cal smoke exhaust smoke exhaust efficiency distance of smokevent visibility
  • 相关文献

参考文献8

二级参考文献61

  • 1洪丽娟,刘传聚.隧道火灾研究现状综述[J].地下空间与工程学报,2005,1(1):149-155. 被引量:84
  • 2彭伟,霍然,胡隆华,王浩波,杨瑞新.隧道火灾的全尺寸试验研究[J].火灾科学,2006,15(4):212-218. 被引量:30
  • 3高峻,谢宝超,徐志胜.杭州过江隧道火灾时人员安全疏散研究[J].防灾减灾工程学报,2007,27(2):159-164. 被引量:22
  • 4GB50157-2003地铁设计规范[S].北京:中国计划出版社,2003.
  • 5DBJ53-14-2005,公路隧道消防技术规程[S].
  • 6蔡加发.公路隧道火灾分析及救灾预案研究[D].重庆:重庆交通大学,2005.
  • 7Jae S R, Hong S R, Dong H K. Critical velocity and burning rate in pool fire during longitudinal ventilation [J]. Tunnelling and Underground Space Technology, 2007, (22) : 262-271.
  • 8Vauquelin O, Wu Y. Influence of tunnel width on longitudinal smoke control [J]. Fire Safety Journal, 2006, (41) : 420-426.
  • 9Lin C J, Chuah Y K. A study on long tunnel smoke extraction strategies by numerical simulation[J]. Tunnelling and Underground Space Technology, 2008, (23):522-530.
  • 10Babrauskas V, Gann R G. A methodology for obtaining and using toxic potency data for fire hazard analysis [J]. Fire Safety Journal, 1998, 31 (3): 45 - 58.

共引文献57

同被引文献66

引证文献12

二级引证文献31

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部