摘要 GIS设备内部缺陷严重影响电网的安全稳定运行,开展GIS设备带电检测及故障诊断技术具有重要意义。结合一起500k V变电站GIS设备异响缺陷实例,通过运用超声波检测、气体组分测试、红外测温以及振动测试等多种带电检测手段进行异响缺陷定位与分析,得出了设备内部由于屏蔽罩松动而引起振动的结论,通过解体验证了结论的正确性。最后,针对此类缺陷提出相应的处理措施和反事故措施,具有较高的现场指导意义。 The safe and stable operation of the power grid are affected by GIS internal discharge, So, developing live testing and fault diagnosis of GIS equipment technology is absolutely necessary and significant. Combined with an example of abnormal sound defect for 500 k V GIS, abnormal sound positioning and analysis is carried out through the use of ultrasonic testing, gas composition testing, infrared temperature and vibration testing and other means, the conclusion that vibration appeared inside of the equipment caused by the loosening of shield is verified by disintegration. Finally, the appropriate countermeasures and anti-accident measures are put forward.
出处 《电气技术》 2014年第11期43-46,54,共5页 Electrical Engineering
关键词 GIS 异响缺陷 带电检测 振动测试 松动 GIS abnormal sound defect live detection vibration testing loosening
  • 相关文献

参考文献5

二级参考文献33

  • 1钱勇,黄成军,江秀臣,肖燕,佐玉华.GIS中局部放电在线监测现状及发展[J].高压电器,2004,40(6):453-456. 被引量:57
  • 2钱勇,黄成军,江秀臣,肖燕.基于超高频法的GIS局部放电在线监测研究现状及展望[J].电网技术,2005,29(1):40-43. 被引量:165
  • 3肖燕,郁惟镛.GIS中局部放电在线监测研究的现状与展望[J].高电压技术,2005,31(1):47-49. 被引量:142
  • 4Joint Working Group 33/23.12. Insulation coordination of GIS: return of experience, on site tests and diagnostic techniques[J]. Electra, 1998, 176(2):67-97.
  • 5Pearson J, Hampton B F, Judd M D, et al. Experience with advanced in-service condition monitoring techniques for GIS and transformers[C] // IEE Colloquium on HV Measurements, Condition Monitoring and Associated Database Handling Strategies. London, UK: IEE, 1998:8/1-8/10.
  • 6Pryor B M. Review of partial discharge monitoring in gas insulated substations[C] // Science, Education and Technology Division Colloquium on Partial Discharges in Gas Insulated Substations. London, UK: [s.n.], 1994: 1-2.
  • 7Boggs S A. Partial discharge: overview and signal generation [J]. IEEE Electrical Insulation Magazine, 1990, 6(4) : 33-39.
  • 8Judd M D, Farish O, Hampton B F. The excitation of UHF signals by partial discharges in GIS[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1996, 3(2): 213-228.
  • 9Lundgaard L E. Partial discharge, XIII: acoustic partial discharge detection-fundamental considerations[J]. IEEE Electrical Insulation Magazine, 1992, 8(4): 25-31.
  • 10国电石嘴山发电厂2×330MW机组技改工程初步设计报告(审定版)[R].西安:西北电力设计院,2006.