风力发电机低电压穿越测试方法研究 被引量:1

Method of Wind Turbine Low Voltage Ride Through Testing Technology
下载PDF
导出
摘要 分析了阻抗分压式电压跌落发生装置(SI-VSG)的设计特性,对比研究了SI-VSG产生的模拟电网故障和真实电网故障特性,发现两者在电网反馈作用、输出阻抗以及相角跳变等方面有着较大的差异。研究显示采用SI-VSG装置进行风电机组低压穿越(LVRT)试验时会产生失真现象,降低了LVRT能力检测的准确性。提出了一种电网故障模拟系统的拓扑结构,使被测风电机组能在接近真实电网环境下进行测试,提高了风电机组的运行可靠性。 The design characteristic of shunt impedance based voltage sag generator( SI-VSG) was analyzed.The fault characteristics of the SI-VSG simulation grid and real power system. Great differences in the power feedback function,the output impedance and phase angle jump etc. were found. SI-VSG used for low voltage ride through( LVRT) test will produce distortion,which can reduce the accuracy of the detection capability of LVRT.Finally,a kind of topological structure for power system fault simulation was put forward,which can be tested in close to real grid for wind turbine and improve the running reliability of wind turbine.
出处 《电器与能效管理技术》 2015年第1期41-45,共5页 Electrical & Energy Management Technology
基金 中-奥(地利)国际合作研究项目(2014DFG62710)
关键词 风力发电 电压跌落发生装置 低电压穿越 电网故障 测试方法 wind power low voltage ride through(LVRT) voltage sag generator grid fault test method
  • 相关文献

参考文献9

  • 1Technische Richtlinie Erzeugungsanlagen am Mittelspannungsnetz [ S ]. 2008.
  • 2DAS A,SCHWARZ M K. Grid connectivity issues and the Importance of GCC [ C]//The 9th meeting of the Grid Coordination Committee,2013:23.
  • 3SALEM T E, FOX J C. Development of a 15 MW hardware in the loop electric grid test facility [ C ] // Proc. Power Conversion and Intelligent Motion,2013:3-9.
  • 4DIAZ M, CARDENAS R. Matrix converter based voltage sag generator to test LVRT capability in renewable energy systems [ C ] // Ecological Vehicles and Renewable Energies ( EVER ), 2013 8th International Conference and Exhibition on. IEEE,2013:1-7.
  • 5Technical Guidelines for Power Generating Units and systems ,Part 3 : Determination of electrical characteristics of power generating units and systems connected to MV, HV and EHV grids[S~.2010.
  • 6ZUBIAGA M,AURTENETXEA S,ETXEGARAI A,et al. LVRT dynamic performance analysis in a detailed time domain simulation scenario beyond the impedance divisor fault [ C ]//Power Electronics and Applications ( EPE ), 2013 15th European Conference on. IEEE ,2013 :1-10.
  • 7KOTSAMPOPOULOS P, HATZIARGYRIOU N, BLETFERIE B, et al. Review, analysis and recommendations on recent guidelines for the provision of ancillary services by Distributed Generation [ C ~// Intelligent Energy Systems (IWIES), 2013 IEEE International Workshop on. IEEE, 2013 : 185-190.
  • 8TANDE J O G, EEK J, MULJADI E, et al. IEA wind annex XXI final technical report [ R 1. IEA Task 21 Final Repor,2007:28.
  • 9ZUBIAGA M,AURTENETXEA S,ETXEGARAI A,et al. LVRT dynamic performance analysis in a detailed time domain simulation scenario beyond the impedance divisor fault [ C ]///Power Electronics and Applications (EPE), 2013 15th European Conference on. IEEE,2013:1-10.

同被引文献5

引证文献1

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部