导出
摘要 某压气站区域性阴极保护系统采用1套4回路外加电流保护方式,阳极地床为柔性阳极和高硅铸铁浅埋辅助阳极地床。为了掌握站内区域阴极保护效果,开展了详细的现场测试,在此基础上对其效果进行了评价,并针对目前存在的部分区域阴极保护不符合要求,以及站内外存在干扰问题进行了数值模拟计算和现场试验研究,确定了整改方案,最终取得了良好整改效果。 A four-circuit impressed current cathodic protection system is applied in a certain compressor station with the anode bed composing of flexible anode and shallowly buried high silicon cast-iron auxiliary anode. In order to realize the protective effect of the regional cathodic protection system,detailed field tests have been carried out. Based on the results of field tests,effect assessment is conducted,then the reform program to solve the problems of inadequate protective effect and interferences between pipelines outside and inside the station is determined by numerical simulation computation and field experiments.
作者 孙冰冰
出处 《石油工程建设》 2014年第6期68-72,共5页 Petroleum Engineering Construction
关键词 压气站 阴极保护 效果评价 数值模拟计算 整改方案 compressor station cathodic protection effect assessment numerical simulation computation reform program
  • 相关文献

参考文献7

  • 1De Giorgi V G, Wimmer S A. Geometric details and modeling accuracy requirements for shipboard impressed current cathodic protection system modeling [J]. Engineering Analysis with Boundary Elements, 2005, 29 (1): 15-28.
  • 2Zamani N G. Boundary element simulation of the cathodic protection system in a prototype ship[J]. Applied Mathematics and Computation, 1988, 26 (2): 119-134.
  • 3邱枫,徐乃欣.用带状牺牲阳极对埋地钢管实施阴极保护时的电位和电流分布[J].中国腐蚀与防护学报,1997,17(2):106-110. 被引量:15
  • 4邱枫,徐乃欣.码头钢管桩阴极保护时的电位分布[J].中国腐蚀与防护学报,1997,17(1):12-18. 被引量:9
  • 5Riemer D P, Orazem M E. A mathematical model for the cathodic protection of tank bottoms[J]. Corrosion Science, 2005, 47 (3) : 849-868.
  • 6Gummow R A. Cathodic Protection Current Requirements For Electrical Grounding Materials [A]. Corrosion/2004 [C]. Houston, Texas: NACE, 2004. 562.
  • 7Kirkpatrick E L, Shamim M L.Copper Grounding Systems Have a Negative Effect on Cathodic Protection in Production Facilities[A]. Corrosion/2000[C]. Houston, Texas: NACE, 2000. 743.

二级参考文献11

  • 1邱枫,徐乃欣.钢质贮罐底板外侧阴极保护时的电位分布[J].中国腐蚀与防护学报,1996,16(1):29-36. 被引量:40
  • 2邱枫,硕士学位论文,1995年
  • 3洪定海,阴极保护实施规范,1987年
  • 4团体著者,金属腐蚀与防护,1979年,3期,57页
  • 5团体著者,金属腐蚀与防护,1976年,2期,28页
  • 6团体著者,中国腐蚀与防护学报,1996年
  • 7邱枫,硕士学位论文,1995年
  • 8团体著者,中国腐蚀与防护学报,1994年
  • 9团体著者,中国腐蚀与防护学报,1993年
  • 10团体著者,长输管道阴极保护工程施工及验收规范, SYJ4006-90

共引文献18