摘要
通过对阳极饱和电抗器的绝缘耐受试验回路和试验方法进行研究,精确、可靠地对ETT(电触发晶闸管)、LTT(光触发晶闸管)换流阀用阳极饱和电抗器进行了以1次/s的速率持续8 h施加冲击电压的绝缘耐受试验。试验结果为超、特高压直流工程换流阀的设计提供了可靠的计算数据和设计依据,供工程技术人员参考。
Through researching the dielectric withstand test circuit and method for the anode saturable reactor,impulse voltage of dielectric withstand test has been applied with 1/s rate of for 8 h to anode saturable reactor which used for ETT(electrically triggered thyristors),LTT(light triggered thyristor)converter valve.The test results provide the reliable calculation data and design basis for the design of EHVDC,UHVDC converter valve,and provide a reference for engineering technical personnel.
出处
《电力电容器与无功补偿》
2014年第6期62-67,共6页
Power Capacitor & Reactive Power Compensation
关键词
阳极饱和电抗器
测试技术
绝缘耐受试验
anode saturable reactor
test technology
dielectric withstand test