可移动式小型液体除湿空调装置的研制 被引量:4

Design of the Small & Movable Liquid Desiccant Air- conditioner
下载PDF
导出
摘要 针对逆流式和叉流式装置在使用中的优势和不足,设计出可以实现结构一体化的小型液体除湿空调装置。经过试验测试,此装置在上海夏季标准环境(干球温度34℃,湿球温度28.2℃)下,用65℃左右的热水作为驱动热源时,制冷量为6~7k W,送风温度在22℃左右,系统热力COP可以达到0.47,电力能效比可达3.4。 Based on the pros and cons of both counter flow and cross flow system,a small and movable liquid desiccant air - conditioner has been designed with an integrated ,ructure. In the Shanghai summer standard environment (dry bulb temperature is 34℃ ,wet bulb temperature is 28.2℃ ) ,the device using the 65℃ hot water as the driving heat source,the cooling capacity is 6 -7kW,the supply air temperature is about 22℃, the Coefficient of Performance (COP)can reach 0. 466 and the Energy Efficiency Ratio(EER) can be up to 4.93.
机构地区 上海理工大学
出处 《流体机械》 CSCD 北大核心 2015年第1期68-71,共4页 Fluid Machinery
关键词 液体除湿空调 结构一体化 试验性能 liquid desiccant air - conditioner an integrated structure performance of experiment