摘要
针对逆流式和叉流式装置在使用中的优势和不足,设计出可以实现结构一体化的小型液体除湿空调装置。经过试验测试,此装置在上海夏季标准环境(干球温度34℃,湿球温度28.2℃)下,用65℃左右的热水作为驱动热源时,制冷量为6~7k W,送风温度在22℃左右,系统热力COP可以达到0.47,电力能效比可达3.4。
Based on the pros and cons of both counter flow and cross flow system,a small and movable liquid desiccant air - conditioner has been designed with an integrated ,ructure. In the Shanghai summer standard environment (dry bulb temperature is 34℃ ,wet bulb temperature is 28.2℃ ) ,the device using the 65℃ hot water as the driving heat source,the cooling capacity is 6 -7kW,the supply air temperature is about 22℃, the Coefficient of Performance (COP)can reach 0. 466 and the Energy Efficiency Ratio(EER) can be up to 4.93.
出处
《流体机械》
CSCD
北大核心
2015年第1期68-71,共4页
Fluid Machinery
关键词
液体除湿空调
结构一体化
试验性能
liquid desiccant air - conditioner
an integrated structure
performance of experiment