数据中心背板空调换热特性分析 被引量:9

Analysis on heat transfer characteristics of backboard air-conditioner in data center
下载PDF
导出
摘要 针对数据中心热管背板空调的传热特性进行分析,首先理论论证背板空调传热量主要受两相换热区面积影响;此外,通过设置多个试验进行测试,证实背板空调以下几个换热特性:背板传热量随着进风温度升高而增加,随着冷冻水流量增加而增加,背板换热量基本不会受到机柜内部服务器布置均匀性影响。 According to the heat transfer characteristics of heat pipe of backboard air- conditioner which is used in the data center, the analysis is conducted. Firstly, heat transfer capacity of backboard air-conditioner is mainly influenced by the area of two-phase heat transfer section, which is verified by theoretical analysis. Secondly, several experiments are set up to confirm the heat transfer characteristics of heat pipe of backboard air-condition er,including that heat transfer capacity increases with the increasing of inlet air temperature and the increasing of chilled water flow,and the heat transfer capacity isn't influenced by the layout uniformity of server inside cabinet.
出处 《制冷与空调》 2015年第1期27-30,69,共5页 Refrigeration and Air-Conditioning
关键词 背板空调 热管 传热性能 数据中心 backboard air-conditioner heat pipe heat transfer characteristic data center
  • 相关文献

参考文献3

  • 1Kandlikar S G. A general correlation for saturated two-phase flow boiling heat transfer inside horizontal and vertical tubes[J]. Journal of Heat Transfer, 1990, 112(2) :219-228.
  • 2Dittus F W,Boelter L M K. Heat transfer in automo- bile radiators of the tubular type [J]. International Communications in Heat and Mass Transfer, 1985,12 (1) :3-22.
  • 3Wang C C, Lee C J, Chang C T, et al. Heat transfer and friction correlation for compact louvered fin-and- tube heat exchangers [J]. International Journal of Heat and Mass Transfer,1999,42(6) :1945-1956.

同被引文献65

引证文献9

二级引证文献32

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部