期刊文献+

顶棚辐射供冷与新风联合系统的辐射顶棚热特性研究 被引量:6

Study on thermal properties of radiation ceiling in ceiling radiant cooling and fresh air combined system
原文传递
导出
摘要 介绍了一种上送上回式新风与顶棚辐射联合供冷系统,通过搭建实验房间,研究了新风系统以及三种不同供水温度对于辐射顶棚的热特性的影响,并且分析了联合系统的防结露能力。实验分析得出,在本次实验条件下,当供水温度高于14℃时,能够保证辐射顶棚不结露。 The paper described an up - supply up - return fresh air and ceiling radiant cooling combined system. The effects of the fresh air system and three different water supply temperatures on the radiant ceiling were studied by setting up an experi- mental room. The condensation proof ability of the combined system was analyzed as well. According to the experiment results, the radiant ceiling is condensation - free when the water temperature is 14℃ under the experiment condition specified in the present paper.
出处 《低温与超导》 CAS 北大核心 2015年第2期79-83,共5页 Cryogenics and Superconductivity
基金 江苏省普通高校研究生科研创新计划项目:辐射供冷与独立新风联合系统控制策略研究(CXLX13_420)
关键词 上送上回 供水温度 结露 联合系统 Up - supply up - return, Water supply temperature, Condensation, Combined system
  • 相关文献

参考文献5

  • 1Anthony Usibelli, Greenberg S, Meal M, etal. Commer- cial - Sector Conservation Technologies [ R ]. Berkeley ;Lawrence Berkeley National Laboratory, 1985.
  • 2Mendell M J. Nonspecific Symptoms in Office Workers: a Review and Summary of the Epidemiologic Literature [J]. Indoor Air, 1993(3) :227 -236.
  • 3寿青云,沈晋明,何婧.辐射供冷加新风系统适用场所与运行控制策略[J].煤气与热力,2008,28(11):A19-A22.
  • 4刘乃玲,刘英杰,方肇洪.顶棚辐射供冷房间人体与环境换热的实验研究[J].制冷学报,2012,33(6):26-31. 被引量:9
  • 5王永红,张爱华,赵羽,袁东立.上部送风在顶棚辐射系统中的应用[J].暖通空调,2013,43(9):87-90. 被引量:6

二级参考文献11

  • 1李欣,罗军.置换通风的应用前景及其适用性分析[C]//全国暖通空调制冷2002年学术年会.全国暖通空调制冷2002年学术年会资料集,2002,11:459-466.
  • 2徐征.低温辐射供冷方式设计问题的探讨.暖通空调,2006,36(10):101-108.
  • 3王予介.低温辐射供暖与辐射供冷[M].北京:机械工业出版社,2004.
  • 4Feustel HE, Stetiu C. Hydronic radiation cooling- preliminary assessment[J]. Energy and Buildings,1995, 22 (3) : 193-205.
  • 5Otesen BW. Possibilities and limitations of radiant floor cooling[J]. ASHRAE Transaction, 1997, 103 (1) : 42-48.
  • 6lmanari T, Omori T, Bogaki K. Thermal comfort and energy consumption of the radiant ceiling panel system: Comparison with the conventional all-air system[J]. Energy and Buildings, 1999, 30 (2) : 167-175.
  • 7Kim T, Kato S, Murakami S. Study on indoor thermal environment office space controlled by cooling panel system using field measurement and the numerical simulation[J]. Building and Environment, 2005, 40 (3): 301-310.
  • 8孔祥雷,张小松,路诗奎.辐射供冷空调结露问题的研究现状及其对策[J].建筑热能通风空调,2008,27(1):20-23. 被引量:28
  • 9康宁,宣永梅,殷清海.辐射供冷现状及发展趋势[J].建筑节能,2009,37(5):74-76. 被引量:16
  • 10李楠,廖建科,郑文茜,刘红.冷却顶板与置换通风复合空调系统的热舒适性分析[J].中南大学学报(自然科学版),2012,43(6):2434-2440. 被引量:9