介绍了一种上送上回式新风与顶棚辐射联合供冷系统,通过搭建实验房间,研究了新风系统以及三种不同供水温度对于辐射顶棚的热特性的影响,并且分析了联合系统的防结露能力。实验分析得出,在本次实验条件下,当供水温度高于14℃时,能够保证辐射顶棚不结露。
The paper described an up - supply up - return fresh air and ceiling radiant cooling combined system. The effects of the fresh air system and three different water supply temperatures on the radiant ceiling were studied by setting up an experi- mental room. The condensation proof ability of the combined system was analyzed as well. According to the experiment results, the radiant ceiling is condensation - free when the water temperature is 14℃ under the experiment condition specified in the present paper.
出处
《低温与超导》
CAS
北大核心
2015年第2期79-83,共5页
Cryogenics and Superconductivity
基金
江苏省普通高校研究生科研创新计划项目:辐射供冷与独立新风联合系统控制策略研究(CXLX13_420)
关键词
上送上回
供水温度
结露
联合系统
Up - supply up - return, Water supply temperature, Condensation, Combined system