基于频域介电谱法的变压器油纸绝缘套管受潮状况分析 被引量:20

Study on Moisture Assessment of Oil-Paper Insulated Bushings Based on Frequency Domain Spectrum
下载PDF
导出
摘要 近年来频域介电谱法(frequency domain spectrum,FDS)作为一种无损检测方法,逐渐被尝试用来检测大型变压器、套管等油纸绝缘设备的绝缘状态。采用该方法对某500 kV变电站主变压器高中压中性点套管及低压故障套管进行了现场离线测量,然后将所测结果与实验室结果进行比对,分析其故障原因,实现了对现场实测数据的定性和定量分析,确认该批次套管存在出厂时套管芯子干燥不充分问题。研究表明,频域介电谱法不仅能够定性地反映套管内部受潮状况和受潮原因,而且还可以对其受潮程度进行定量分析,从而为该方法在实际生产中的进一步应用提供了理论和实践基础。 In recent years,the frequency domain spectrum( FDS) as a non-destructive method has been gradually applied to the oilpaper insulation assessment of power equipment such as power transformers and bushings. In this paper,FDS method has been applied to the insulation condition assessment of neutral bushings and low-voltage bushings of an off-line transformer in a 500 kV substation,and then the result is compared with that obtained in laboratory to find the cause of fault through the qualitative and quantitative analysis of the field data. It is confirmed that the condenser bodies of the batch of investigated bushings are insufficient drying. It is considered that FDS method is not only adequate for qualitatively reflecting the wetting condition in oil-paper insulation of bushings,but also for quantitative assessment of moisture content of bushings,and provides the theoretical and practical basis for the future application of this method in practice.
出处 《南方电网技术》 2014年第4期52-56,共5页 Southern Power System Technology
关键词 电容型套管 油纸绝缘 频域介电谱 受潮 水分含量 capacitive-type bushing oil-paper insulation frequency domain spectrum wetting moisture content
  • 相关文献

参考文献10

二级参考文献65

  • 1李立浧.直流输电技术的发展及其在我国电网中的作用[J].电力设备,2004,5(11):1-3. 被引量:43
  • 2李季,罗隆福,许加柱,李勇,姚远.换流变压器阀侧绝缘电场特性研究[J].高电压技术,2006,32(9):121-124. 被引量:44
  • 3王小凤,周浩.±800kV特高压直流输电线路的电磁环境研究[J].高压电器,2007,43(2):109-112. 被引量:51
  • 4王冰,王清璞,孙优良.换流变压器阀侧绕组端部极性反转瞬态电场的计算与分析[J].变压器,2007,44(6):11-15. 被引量:22
  • 5DL/T596-1996电力设备预防性试验规程[S].北京:中国电力出版社,1996.
  • 6KALOCSAL L.Spectrum of Polarization Phenomena of Long Time-constant as a Diagnostic Method of Oil-paper Insulation System[C].Proceeding of the 3rd International Conference on Properties and Application of Dielectric Materials.Tokyo, Japan:IEEE Dielectrics and Electrical Insulation Society and Insitute of Electrical Engineens of Japan, 1991:723-726.
  • 7NEMETH E.Measuring Voltage Response: a Non-destructive Diagnostic Test Method of HV Insulation[J].IEE Proceeding of Science.Measurement and Technology, 1999,146(5) :249-252.
  • 8Tokyo Electric Co. Inc Hitachi,Ltd.A Diagnostic Method Based on RVM (Return Voltage Measurement)for Condenser Bushing with Oil-Paper Insulation Systems[J].Electric Engineering in Japan, 2000,130( 1 ) : 21-29.
  • 9ASCHENBRENNER V.Using of Parameters of RVM Measurement for Qualitative Appreciation of Power Transformers Insulation States[C].Transmission and Distribution Conference and Exhibition.2002,1 829-1 833.
  • 10OMAR HASSANL,HOSSEIN BORSIL,EMST GOCKENBACH, et al.Diagnostic of Insulation Condition of oil Impregnated Paper Insulation System with Return Voltage Measurements[C].2003 Annual Report Conference on Electrical Insulation and Dielectric Phenomena.USA : IEEE Dielectrics and Electrical Insulation Society,2003 : 153-156.

共引文献76

同被引文献210

引证文献20

二级引证文献153

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部