高压直流单极运行对某220kV变电站的影响分析

Impact of HVDC Monopole Operation on Certain 220 kV Substation
下载PDF
导出
摘要 高压直流输电可引起变压器直流偏磁问题。为定量描述直流偏磁对变压器的影响,介绍了所采用的土壤模型及接地极电位分布,详细阐述了"二层地"结构下的电位计算方法,并针对单环、双环接地计算出大地电位。分析了500 kV天广直流在单极接地运行方式下对220 kV某变电站的影响,得出该运行方式对该站的严重影响。 Power transmission with high voltage direct current(HVDC)can cause transformers DC bias.This article introduces the model used in the soil and the ground electrode potential distribution,it also calculates the ground voltage in the case of a single and double ring grounding.Besides this paper describes the potential level of the two layers of soil structure calculation method and uses this method to analyze the influence of 220 kV substation under the 500 kV Tian-Guang HVDC monopole operation mode.The conclusion is that the operation mode has seriously affected the substation.
出处 《陕西电力》 2014年第6期65-68,共4页 Shanxi Electric Power
基金 国家重点基础研究发展计划(973计划)项目资助(2012CB215200)
关键词 高压直流输电 单极运行 直流偏磁 土壤电位 变压器 HVDC power transmission monopole operation DC bias soil potential power transformer