期刊文献+

低环境温度空气源热泵机组在北京冬季运行的性能 被引量:23

Running performance of low-temperature air-source heat pump applied in winter of Beijing
下载PDF
导出
摘要 2013年供暖季,对安装在北京某办公建筑中的一台采用中间补气的涡旋压缩机准双级压缩空气源热泵热水机组进行了实际性能测试。对制热量、耗电量等性能参数进行了统计分析,结果表明:该空气源热泵机组在测试期间运行稳定,平均出水温度为42.0℃,供热季节能效比HSPF约为3.20kW·h/(kW·h);在室外温度为-8℃时的能效比仍能保持在2.8kW·h/(kW·h)以上,说明采用中间补气的低环境温度空气源热泵机组在北京作为冬季供暖热源具有较好的运行性能。 Tests an air-source heat pump with a compensating scroll compressor of quasi two-stage compression in an office building of Beijing during nearly the whole heating season of 2013.By analysing the heating capacity,energy consumption and other performance parameters,concludes that the air-source heat pump has been running steadily during the testing period,and the average temperature of supply water is 42.0 ℃,and heating seasonal performance factor (HSPF)is about 3.20 kWh/kWh.The coefficient of performance can remain more than 2.8 kWh/kWh when outdoor temperature is -8 ℃,which proves that the air-source heat pump with scroll compressor of quasi two-stage compression shows good running performance as heating device in Beijing.
出处 《暖通空调》 北大核心 2015年第3期52-58,共7页 Heating Ventilating & Air Conditioning
基金 国家自然科学基金资助项目(编号:51176084 51006059)
关键词 空气源热泵 低环境温度 制热 现场测试 运行参数 能效比 air-source heat pump low-temperature environment heating field test operation parameter energy efficiency ratio
  • 相关文献

参考文献15

二级参考文献37

共引文献229

同被引文献239

引证文献23

二级引证文献115

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部