期刊文献+

数据中心热管背板空调应用实测研究——系统不平衡运行分析 被引量:13

Experimental study on application of heat pipe backboard air-conditioner in data center—analysis of unbalance operation in system
下载PDF
导出
摘要 介绍用于数据中心的热管背板空调系统,理论分析背板空调运行中的不平衡问题,并且通过试验进行应用性研究,证明热负荷分布极度不平衡时,背板蒸发器上部位置将会处于严重的过热干烧状态,指出相对均匀的热负荷布置可以解决这一问题。 The heat pipe backboard air-conditioner system used in the data centers is briefly described. The unbalance operation of backboard air-conditioner is analyzed theo- retically, and application research is conducted by experiments. It is proved that when the heat load distribution is extremely uneven, backboard evaporator's upper position is in a serious overheat and dry burning state, and the relatively uniform arrangement of heat load can solve this problem.
出处 《制冷与空调》 2015年第3期22-25,12,共5页 Refrigeration and Air-Conditioning
关键词 数据中心 背板空调 热管 传热性能 data center backboard air-conditioner heat pipe heat-transfer performance