配电变压器标识容量小于真实容量的判断方法 被引量:1

Judge Method for Wrong-Labeled Capacity of Distribution Transformer
下载PDF
导出
摘要 针对配电变压器大容量标成小容量问题,对累积的抽检试验数据进行了分析,阐述了配电变压器直流电阻、空载损耗、负载损耗与配电变压器容量的关系,并提出了配电变压器容量错标的综合判断方法。试验结果表明,综合利用直流电阻、空载损耗、负载损耗试验数据可较为可靠地判断配电变压器标示容量是否小于实际容量。 For the problem of large capacity distribution transformer marked as a small capacity, this paper analyzed the accumulated sam-pling test data, described the relationship among DC resistance, no-load loss, load loss and variable capacitor of distribution transformer, and put forward a comprehensive judgment method of distribution wrong-labeled capacity. The test result shows that the comprehensive utiliza-tion of DC resistance, no-load loss and load loss test data can more reliably determine whether the distribution transformer capacity labeled is less than the actual capacity.
出处 《电工电气》 2015年第4期31-34,41,共5页 Electrotechnics Electric
关键词 配电变压器 容量错标 直流电阻 空载损耗 负载损耗 distribution transformer wrong-labeled capacity DC resistance no-load loss load loss
  • 相关文献

参考文献4

二级参考文献10

  • 1Q/CSG11624-2008,配电变压器能效标准及技术经济评价导则[S].
  • 2GB/T10228-2008.干式电力变压器技术参数和要求[S].
  • 3GB/T22072-2008.干式非晶合金铁心配电变压器技术参数和要求[S].
  • 4同济大学应用数学系.数理统计与随机过程[M].上海:同济大学出版社,2002.
  • 5Cardoso B P, Salles C, Martinez M L B,et al. Distribution transformers performance[J]. Power Tech,2005 IEEE Russia,27-30 June 2005 Page(s):1-6.
  • 6Murray R, Schiller J J, Srinivasan A. Probability and statistics[M]. New York McGraw-Hill Professional,2001.
  • 7GB/T6451--2008,油浸式电力变压器技术参数和要求[S].
  • 8GB1094.1-1996,电力变压器第1部分总则[S].
  • 9王旭军,陈国钧.非晶铁心配电变压器空载损耗与其容量的关系[J].变压器,2002,39(2):8-11. 被引量:5
  • 10曹玉泉,付光杰.S9系列电力变压器空载损耗与其容量的关系[J].变压器,1999,36(4):5-7. 被引量:3