摘要
应用API579-2007《合于使用》中的火灾损伤评价方法,对某炼油厂的一座过火减压塔进行了合于使用评价。本评价将过火减压塔划分为6个热暴露区,结果显示:Ⅰ~Ⅳ区域免于评价,允许继续使用;V级区域可以继续使用;VI级区域不满足继续使用的标准,应更换新钢板后重新检测并符合标准规定,方能继续投入使用。
Fitness for service assessment of a fire vacuum tower in oil refinery was carried out by applying fire damage evaluation method from API 579--2007 Fitness-for-Service. In this assessment, the fire vacu- um tower was divided into six heat exposure zones. The assessment results showed that zones I ~IV were free to evaluation, zone V can continue to use and zone VI should replace for new plates and have re - examination to continue to put into use because it does not meet the use standard.
出处
《压力容器》
2015年第4期66-72,共7页
Pressure Vessel Technology
基金
国家质量监督检验检疫总局公益性行业科研专项经费项目(201310162)
中国特种设备检测研究院博士基金(BSJJ-2013-02)
关键词
过火
减压塔
合于使用评价
热暴露区
fire
vacuum tower
fitness for service
heat exposure zone