摘要 为了提高发现油浸式变压器潜伏性绝缘缺陷的能力,研究振荡型冲击电压下典型油纸绝缘缺陷的放电特性,掌握振荡型冲击电压下局部放电的特点和规律,提出了振荡型冲击电压试验同时进行局部放电检测的方法,开发了基于振荡型冲击电压的变压器局部放电检测系统,解决了局部放电脉冲的完整测量问题,初步实现了对局部放电的辨识和绝缘状态诊断。应用结果表明:该系统对于发现油浸式变压器绝缘缺陷是有效的。 In order to improve the ability of finding hidden insulation defect of oil-immersed transformer,researches the discharge property of typical oiled paper insulation defect under oscillatory impulse voltage,masters the characteristc and law of partial discharge under oscillatory impulse voltage,puts forward the measuring method of partial discharge when making oscillatory impulse voltage test,develops transformer partial discharge detection system based on oscillatory impulse voltage,solves problem of complete measurement for partial discharge pulse voltage,realizes preliminary the distinguishment of partial discharge and diagnosis of insulation state,the site application result shows that the system detecting insulation defect of oil-immersed transformer is effective.
出处 《宁夏电力》 2015年第2期6-13,共8页 Ningxia Electric Power
基金 宁夏回族自治区科技成果(2012189) 宁夏回族自治区2012年度科学技术进步二等奖
关键词 油浸式电力变压器 振荡型冲击电压 局部放电测量 oil -immersed transformer oscillatory impulse voltage measurement of partial discharge
  • 相关文献

参考文献7

  • 1吴旭涛,李秀广,艾绍贵.油浸式变压器现场振荡型冲击耐压试验方法[J].宁夏电力,2014(2):1-6. 被引量:4
  • 2DL474.6-92,变电器操作波感应耐压试验Es].
  • 3黄齐嵩,喻剑辉.变电器操作波感应耐压试验的几个问题[J].武汉水利电力学院学报,1978,8(2):75-82.
  • 4郭满生.大型电力变压器操作冲击试验的一些改进[J].变压器,1998,35(1):6-8. 被引量:3
  • 5王敬侃.变电器做操作波试验时等效电容的估算[J].高电压技术,1979,5(3):23-31.
  • 6黄齐嵩.变电器进行操作波感应耐压试验时等效电容的计算[J].高电压技术,1979,5(3):32-37.
  • 7陈道辉,梅良栋.高压电器产品的操作波试验[J].变压器,1980,17(1):17-20.

二级参考文献2

共引文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部