摘要 以焓差实验室为平台,以建筑凹槽内某型号室外机为研究对象,通过实验研究分体式空调室外机在不同安装位置和不同凹槽封闭百叶形式下的周围热环境及空调器的EER.实验结果表明:该型号室外机和墙体之间的间距应大于80 mm,随着两者间距的增大,空调器的散热量、制冷量和EER也随之升高;室外机排风扇距百叶300 mm左右时,系统运行状况最佳;百叶开度为30°左右时,空调散热效果最好,同时随着百叶间距的增大,空调散热效果增强. This study was based on the enthalpy difference lab, with a certain type of outdoor machine in the building groove as the research object, through the experimental study the thermal environment surrounding outdoor machine and the EER in different locations and the different louver form in the groove. The experimental results show that the distance between the certain type of outdoor machine and the wall should be more than 80 mm, with the increase of the distance, quantity of heat, air conditioner refrigerating capacity and EER was increased. When the outdoor machine fan from the shutter is about 300 mm, the running condition of the system is best. When the shutter opening is 30°, the cooling effect air conditioning is best. At the same time with the increase of the louver spacing, the heat dissipation air conditioning is greatly enhanced.
出处 《西安建筑科技大学学报(自然科学版)》 CSCD 北大核心 2015年第2期282-286,308,共6页 Journal of Xi'an University of Architecture & Technology(Natural Science Edition)
基金 韩国国土海洋部尖端城市开发研究项目(Code#09R&D A01)
关键词 室外机 安装位置 百叶形式 室外机周围热环境 outdoor unit installation location louvers form outdoor unit surrounding thermal environment
  • 相关文献

参考文献11

  • 1周德海,邵晓亮,张晓灵,李先庭,石文星,王宝龙.建筑凹槽中室外机周围热环境的数值模拟[J].广州大学学报(自然科学版),2010,9(6):17-22. 被引量:24
  • 2展圣杰.民用分体式空调室外机安装条件对散热影响的研究[D].杭州:浙江大学,2012.
  • 3CHOW T T,LIN Z.Predietion of on-coil temperature of condensers installed at tall building re-entrant[J].APPlied Thermal Engineering,1999,(19):117-132.
  • 4CHOW T.T,LIN Z,LIU J.P.Effect of building re-entrant shape on performance of air-cooled condensing units[J].Energy and building,2000,(32):143-152.
  • 5CHOW T T,LIN Z,LIU J P.Effect of condensing unit layout at building re-entrant on split-type air-conditioner performance[J].Energy and Buildings,2002(34):237-244.
  • 6CAC Laboratory,LG Electronics Inc.Optimum placement of top discharge outdoor unit installed near a wall[J].Energy and buildings,2013(59):228-235.
  • 7CHOI Seok Ho,LEE Kwan Soo,KIM Byung-Soon.Effects of stacked condensers in a high-rise apartment building[J].Energy,2004(30):968-981.
  • 8程卓明,黄钊,马勇.百叶窗开度对室外机运行环境影响分析[J].暖通空调,2009,39(1):133-135. 被引量:22
  • 9GB/T7725-2004,房间空气调节器[S].北京:中国标准出版社.2005.
  • 10谷德军,王剑波,朴完奎,刘杨,金梧凤.室外机室格栅对空调运行环境的影响[J].绿色科技,2012,14(6):271-274. 被引量:8

二级参考文献25

  • 1王文魁,谢鸣,阮立明.空调室外机散热对建筑物红外特征的影响[J].节能技术,2005,23(3):244-246. 被引量:7
  • 2姜彩玲,陈江平,陈芝久,田杰,欧阳华,杜朝辉.分体式空调室外机空气流场特性[J].上海交通大学学报,2005,39(8):1226-1228. 被引量:6
  • 3杭寅,刘东,黄艳,刘俊.某高层建筑空调室外机的气流模拟及优化[J].建筑热能通风空调,2006,25(3):12-16. 被引量:15
  • 4Abdollah Avara,Ehsan Daneshgar.Optimum placement of condensing units of split-type air-conditioners by numerical simulation.Energy and Buildings,2008,40:1268-1272.
  • 5T T Chow,Z Lin,Q W Wang.Studying thermal performance of split-type air-conditioners at building re-entrant via computer simulation∥Sixth international IBPSA Conference Kyoto.Japan,1999:1357-1363.
  • 6Gang Wang,Yafeng Hu,Songtao Hu.Thermal environment of outdoor units of VRV system in high-rise building∥Proceedings:Building Simulation 2007.2007:1109-1114.
  • 7H Xue,B Xu,J Wu,et al.Prediction of temperature rise near condensing units in the confined space of a high-rise building.Building and Environment,2007,42:2480-2487.
  • 8T T Chow,Z Lin,J P Liu.Effect of condensing unit layout at building re-entrant on split-type air-conditioner performance.Energy and Buildings,2002,34:237-244.
  • 9T T Chow,Z Lin,Q W Wang.Effect of building re-entrant shape on performance of air-cooled condensing units.Energy and Buildings,2000,32:143-152.
  • 10陶文铨.数值传热学.2版.西安交通大学出版社.2004.