期刊文献+

变电站集中监控模式下告警信息的优化处理 被引量:12

Optimization Treatment of Alarm Information in Centralized Monitoring Mode of Substation
下载PDF
导出
摘要 针对变电站集中监控模式下,告警信息存在信息量巨大,干扰信息多,信息频发、误发等问题,提出将告警信息进行分类管理、加延时、修改限值、挂牌屏蔽、单点抑制等信息优化处理措施,分析实际运行结果,说明告警信息优化措施正确、可行,有效提升了变电站设备安全运行的实时监视水平。 According to the problems of a huge amount of alarm information, a lot of interference information, the frequent and the false information in the centralized monitoring of substation, this paper proposes a series of processing methods containing classification management, plus time delay, modifying limit, posting placard to shield information, single-point suppression. The practical operation results show that the optimization technology of alarm information is correct and feasible,which could also improve real time monitoring level of substation equipment effectively.
出处 《河北电力技术》 2015年第1期23-24,27,共3页 Hebei Electric Power
关键词 变电站 集中监控 告警信息 信息优化 伪告警 substation centralized monitoring alarm information information optimization false alarm
  • 相关文献

参考文献4

二级参考文献21

  • 1林嘉宜,彭宏,谢嘉孟,郑启伦.不确定时态信息表示的统一模型[J].计算机应用,2005,25(3):611-614. 被引量:9
  • 2文福拴,韩祯祥.基于遗传算法和模拟退火算法的电力系统的故障诊断[J].中国电机工程学报,1994,14(3):29-35. 被引量:99
  • 3文福拴,韩祯祥.基于覆盖集理论和Tabu搜索方法的电力系统警报处理[J].电力系统自动化,1997,21(2):18-23. 被引量:30
  • 4LAMBERT T G, FONSECA E F, COUTINHO M P, et al. Intelligent alarm processing// Proceedings of 2006 Internationa Conference on Power System Technology, October 22-26, 2006, Chongqing, China: 1-6.
  • 5MIAO H J, SFORNA M, LIU C C. A new logic-based alarm analyzer for on-line operational environment. IEEE Trans on Power Systems, 1996, 11(3): 1600 1606.
  • 6LIU C C, SFORNA M, MIAO H J. On-line fault diagnosis using sequence-of-events recorder information// Proceedings of 1996 International Conference on Intelligent Systems Applications to Power Systems, January 28-February 2, 1996, Orlando, FL, USA: 339-344.
  • 7MCDONALD J R, BURT G, YOUNG D J. Alarm processing and fault diagnosis using knowledge based systems for transmission and distribution network control. IEEE Trans on Power Systems, 1992, 7(3): 1292-1298.
  • 8YANG H T, CHANG W Y, HUANG C L. A new neural networks approach to on line fault section estimation using information of protective relays and circuit breakers. IEEE Trans on Power Delivery, 1994, 9(1): 220-230.
  • 9YANG H T, CHANG W Y, HUANG C L. Power system distributed on-line fault section estimation using decision tree based neural nets approach. IEEE Trans on Power Delivery, 1995, 10(1): 540-546.
  • 10WEN Fushuan, CHANG C S, FU Weihui. New approach to alarm processing in power systems based on the set covering theory and a refined genetic algorithm. Electric Machines and Power Systems, 1998, 26(1) : 53-67.