摘要 防跳回路能够有效地避免断路器"跳跃"的发生,但如果防跳回路设计不合理,会引起防跳回路失效从而无法实现防跳功能。针对现场遇到的一起防跳回路异常情况,提出了3种解决方法,并对各种方法进行实际分析,建议在监视回路中串接一防跳继电器常闭结点,现场证明该方法具是合理和有效的,保证了电网的安全运行。 The anti-bouncing circuit of the breaker can avoid the occurrence of frequent kick-downs effectively. If the design of anti- bouncing circuit is unreasonable or the parameters of the anti-bouncing relay do not match to the control loop,the function of the anti-bouncing will lose. In the light of the abnormality in anti-bouncing circuit, three solutions are put forward. After the analysis to above-mentioned solutions, it is suggested to connect one normally-closed node in series in monitor circuit. The site practice has proved that the method is reasonable and effective, can ensure the safe operation of power grid.
作者 龙启峰
出处 《陕西电力》 2015年第5期85-87,共3页 Shanxi Electric Power
关键词 跳跃 防跳回路 防跳继电器 控制回路 自保持回路 kick-down anti-bouncing circuit anti-bouncing relay control loop self-holding loop