期刊文献+

复合材料电杆在山区配电网中的应用 被引量:4

Application of Composite Pole in Mountainous Distribution Line
下载PDF
导出
摘要 论述了复合材料电杆在山区配电网中的应用。为解决山区杆塔的运输安装困难以及减少雷击污闪故障,对复合材料杆塔的电气、机械特性作了试验。试验结果表明:聚氨酯复合材料电杆在受潮、淋雨等条件下,具有良好的绝缘性,因而可以提高线路的绝缘水平。与常规钢筋混凝土电杆相比,冲击放电电压增加了约5.9倍,爬电距离增加了3.2倍;杆塔的整体强度满足各工况下荷载的要求。一条10kV的12基复合材料电杆线路已在南网挂网运行,情况良好。 This paper illustrates the application of the composite pole in mountainous distribution line. In order to solve the difficulty in transportation and installation of the poles and to reduce the pollution flashover fault caused by lightning strike ,the electrical and mechanical properties of composite tower were tested. The results shows that the polyurethane composite pole can remain its insulativity under the condition of damp or raining, thus it can increase the insulation level of pole. Compared with conventional reinforced concrete pole, The composite pole's impact discharge voltage increases about 5.2 times, and its ereepage distance of phase-ground increases about 3. 2times. The whole strength of pole can meet the load requirements in various conditions. A 10 kV composite pole with 12 bases has been operating in southern power network in good condition.
出处 《吉林电力》 2015年第3期30-34,共5页 Jilin Electric Power
关键词 复合材料 聚氨酯 配电线路 雷击闪络 污闪 钢筋混凝土杆 composite materials polyurethane distribution line lightning flashover pollution flashover steelconcrete pole
  • 相关文献

参考文献7

  • 1夏开全.复合材料在输电杆塔中的研究与应用[J].高科技纤维与应用,2005,30(5):19-23. 被引量:99
  • 2邓世聪,刘庭,李汉明,魏前虎,胡广生,刘凯,肖宾.110kV架空输电线路复合材料杆塔的材料、电气和机械特性试验[J].南方电网技术,2011,5(3):36-40. 被引量:43
  • 3GB/T50061-2010,66kV及以下架空电力线路设计规范[S].
  • 4杨保珍.关于云南省输电线路采用综合防雷装置的历史回顾及运行分析[C].送电线路防雷接地技术文集,北京:出版者不详,2001:57-58.
  • 5杜正东.高压架空输电线路防雷研究[C].2007年全国架空输电线路技术交流研讨会交流文集,北京:出版者不详,2007:257-297.
  • 6GB/T50064-2014,交流电气装置的过电压和绝缘子配合设计规范[S].
  • 7定额站.20kV及以下配电网工程预算定额(第三册)架空线路工程[M].北京:中国电力出版社,2009:3.62.

二级参考文献14