上海某办公楼土壤源热泵系统冬季运行特性实测分析 被引量:6

Winter performance analysis for a ground-coupled heat pump system of an office building in Shanghai
下载PDF
导出
摘要 通过对上海市某办公楼土壤源热泵系统冬季工况的长期监测,分析了土壤源热泵系统在上海市办公类建筑下的长期运行特性.监测结果显示,冬季工况下,日均部分负荷率有80%的时间都处于40%-80%负荷率下,40%负荷率的时间最长,占整个冬季工况的23.3%.机组能效比为3.8-6.7,系统能效比为1.9-4.7.能效比不仅受部分负荷率和地埋管出水温度影响,受用户侧出水温度影响也较大.因此基于建筑负荷,合理设置机组和水泵开启台数及合理设置用户侧出水温度对土壤源热泵系统高效运行具有重要意义. Based on the work of on-site monitoring under winter condition, the long-term operation performance of an office building with ground-coupled heat pump system in Shanghai is analyzed. The result shows, during the monitoring period, the daily average partial load ratio (PLR) of the ground heat pump system was almost at 40%-80%, accounting for about 80% of the winter-time. And the value of PLR was mostly at 40%, about 23.2% of the winter-time; the unit daily performance factor (DPF) was between 3.8 and 6.7, and the system DPF was varying from 1.9 to 4.7. Furthermore, it is found that the DPF was affected by not only the PLR, but also by the user-side supply water temperature. Therefore, based on the building load, rational operation of unit and pump as well as rational setting of user-side supply water temperature are significant to the high operating performance of the ground-coupled heat pump system.
出处 《西安建筑科技大学学报(自然科学版)》 CSCD 北大核心 2015年第3期413-417,432,共6页 Journal of Xi'an University of Architecture & Technology(Natural Science Edition)
基金 "十二五"国家科技支撑计划项目(2011BAJ03B02-1)
关键词 长期监测 能效比 日均部分负荷率 地埋管出水温度 用户侧出水温度 daily performance factor partial load ratio buried pipes outlet water temperature user-side supply water temperature
  • 相关文献

参考文献16

二级参考文献55

共引文献154

同被引文献27

引证文献6

二级引证文献14

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部