大容量离相封闭母线轴向焊接与电动力分析 被引量:5

Analyses on Axial Welding and Electromagnetic Force of Large Capacity Enclosure Type Isolated-phase Bus
下载PDF
导出
摘要 随着发电机组容量越来越大,短路故障中离相封闭母线所受电动力也变得更大。在离相封闭母线的相关国家和行业标准中,对母线轴向焊缝焊接要求不明确。文中结合国内某1 250 MWe级核电项目离相封闭母线技术参数,对母线进行了短路故障下的受力分析,同时提出了大容量离相封闭母线轴向焊缝焊接要求建议。 The larger the capacity of a generating unit is, the greater the electromagnetic force on the enclosure type isolated-phase bus becomes in short circuit fault condition. In the related national and industrial standards with enclosure type isolated-phase bus, the requirements for axial welding are unclear. In this paper, a force analysis of the enclosure type isolated-phase bus in short circuit condition is conducted for a 1 250 MWe nuclear power project, and some suggestions are provide for axial welding requirements of large capacity enclosure type isolated-phase bus.
作者 严兆君 吴军
出处 《高压电器》 CAS CSCD 北大核心 2015年第7期78-80,86,共4页 High Voltage Apparatus
关键词 离相封闭母线 轴向焊缝 短路电动力 正应力 enclosure type isolated-phase bus axial weld short circuit electromagnetic force normal stress
  • 相关文献

参考文献5

  • 1GB/T8349--2000金属封闭母线[S].北京:中国标准出版社,2000.
  • 2JB/T9639-1999封闭母线[S].北京,机械工业出版社.1999.
  • 3发电教研室大电流母线科研小组.全连外壳式分相封闭母线在短路时外壳和母线导体所受电动力的分析和计算[J].西安交通大学学报,1974,6(3):35·58.
  • 4吴励坚.离相封闭母线短路时的外壳电动力的分析和计算[J].西安交通大学学报,1984,18(1):101-110.
  • 5GB/T3190-2008变形铝及铝合金化学成分[S].北京:中华人民共和国国家质量监督检验检疫总局,2008.