某多晶硅厂生活污水再生处理工程实例

Project case of the treatment and reusing of domestic sewage in a polysilicon plant
下载PDF
导出
摘要 某多晶硅厂采用A/O生物接触氧化法处理生活污水,联合后续的混凝沉淀和过滤工艺,主要污染物COD、BOD、NH3-N、SS分别降至50、10、10、10 mg/L以下,达到《城市污水再生利用城市杂用水水质》(GB/T 18920—2002)要求。出水用于厂区的景观水池、绿化、冲厕等。该厂平均每月回用中水约9 500 m3,可节省水费约4.43万元。系统通过PLC、在线仪表实时监控水质,其操作方便、运行稳定,具有明显的经济效益和环境效益。 The A/O bio-contact oxidation process has been used for treating the domestic sewage in a polysilicon plant. Combined with the subsequent coagulation sedimentation and filtration processes,the concentrations of main pollutants,such as COD,BOD,NH3-N and SS can be decreased to lower than 50,10,10,10 mg/L,respectively,reaching the Reuse of Urhan Recycling Water—Quality Standard of Urban Miscellaneous Water Consumption(GB/T18920—2002). The effluent can be used in landscape ponds,greenbelts,flushing toilets,etc. in the plant area. The amount of reclaimed water is about 9 500 m3 a month,i.e. CNY44 300 of water cost can averagely be saved every month. The water quality is real-time monitored and controlled through the PLC and online instruments. The system is characterized by simple operation and stable running,having obvious economic and environmental benefits.
出处 《工业水处理》 CAS CSCD 北大核心 2015年第7期99-101,共3页 Industrial Water Treatment
关键词 生活污水 中水回用 A/O接触氧化 domestic sewage reclaimed water reuse A/O bio-contact oxidation