隔离型阻燃电缆燃烧性能检测 被引量:1

Burning Behavior Test for Isolated Flame Retardant Cable
下载PDF
导出
摘要 介绍隔离型阻燃电缆的结构及性能:采用创新型的阻燃材料填充及隔离,使得电缆线芯绝缘受到完整保护而难以参与燃烧反应,不仅可满足GB/T 18380.33-2008/IEC 60332-3-22:2000《电缆和光缆在火焰条件下的燃烧试验第33部分:垂直安装的成束电线电缆火焰垂直蔓延试验A类》中成束阻燃A类每米试样非金属材料体积7 L的要求,也能顺利通过国家标准GB 31247-2014《电缆及光缆燃烧性能分级》B1级试验。 The paper introduces construction and performance of isolated flame retardant cable. The cable is filled and isolated with innovative flame retardant materials, which protects the cable core insulation from burning. It not only complies with the Tests on Electric and Optical Fiber Cables under Fire Conditions- Part 33: Test for Vertical Flame Spread of Vertically-mounted Bunched Wires or Cables- Category A (GB / T 18380. 33 - 2008 / IEC 60332 - 3 -22: 2000) which specifies that the volume of non- metallic materials of bunched flame retardant class A sample should be 7 L per meter, but also passes the Bl level test specified in Behavior of Electrical and - 2014). Classification for Burning Optical Cables (GB 31247 - 2014).
出处 《建筑电气》 2015年第7期28-30,共3页 Building Electricity
关键词 隔离型阻燃电缆 燃烧性能分级 金属 氢氧化物 火焰蔓延(FS) 燃烧增长速率指数 (FIGRA) 产烟速率峰值(SPR峰值) 受火1200s内 的产烟总量(TSP1200) 热释放速率峰值(HRR峰值) isolated flame retardant cable classification for burning behavior metall hydroxid flame spread (FS) fire index growth rate (FIGRA) smoke production rate peak (SPR peak) total smoke production affected by fire for 1 200 s (TSP1200) heat release rate peak (HRR peak)
  • 相关文献

参考文献3

  • 1公安部四川消防研究所,等.GB31247-2014电缆及光缆燃烧性能分级[S].北京:中国标准出版社,2015.
  • 2公安部四川消防研究所.GB/T31248-2014电缆或光缆在受火条件下火焰蔓延、热释放和产烟特性的试验方法[S].北京:中国标准出版社,2015.
  • 3上海电缆研究所.GB/T18380.33-2008/IEC60332-3-22:2000电缆和光缆在火焰条件下的燃烧试验第33部分:垂直安装的成束电线电缆火焰垂直蔓延试验A类[S].北京:中国标准出版社,2008.

共引文献3

同被引文献4

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部