摘要 分析了SF6气体绝缘金属封闭开关设备(gas insulated metal enclosed switchgear and controlgear,GIS)局部放电产生的原因,结合现场应用实例,对2种GIS局部放电在线检测技术——超声波检测技术和特高频检测技术进行了应用比较,结果表明特高频检测法灵敏度高、抗电磁干扰能力强、有效测量范围大,能准确检测GIS内部绝缘缺陷,适用于长期在线监测;超声波检测法定位准确,可作为特高频检测法的补充和辅助手段;2种方法综合利用可有效发现绝缘缺陷并实现准确定位。 Reason for partial discharge of SF6 gas insulated metal enclosed switchgear and controlgear(GIS)was analyzed.Combining field application example,application comparison of two kinds of GIS partial discharge online detection technologies including ultrasonic detection technology and ultrahigh frequency detection technology was made.Results indicate that ultrahigh frequency detection method is of high sensitivity,strong anti-electromagnetic interference ability and large effective measuring range which is able to correctly detect internal insulation defect of GIS and suitable for long-term online detection,while ultrasonic detection method is accurate for positioning which is able to be taken as supplement for ultrahigh frequency detection method.Insulation defect could be effectively discovered and correct positioning be realized by means of comprehensive usage of these methods.
出处 《广东电力》 2015年第7期88-90,共3页 Guangdong Electric Power
基金 国网四川省电力公司科技项目(5219991308DN)
关键词 局部放电 气体绝缘金属封闭开关设备 超声波检测法 特高频检测法 partial discharge gas insulated metal enclosed switchgear and controlgear ultrasonic detection method ultrahigh frequency detection method
  • 相关文献

参考文献5

二级参考文献4

  • 1刘卫东,95全国设备诊断技术学术会议论文集.上,1995年
  • 2覃剑,高电压技术,1995年,21卷,3期
  • 3龙家聪,电气设备绝缘在线测试技术和应用实例资料选编,1988年
  • 4吕建,高电压技术,1987年,1期

共引文献81

同被引文献59

引证文献4

二级引证文献16

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部