绝缘油老化程度对变压器绝缘系统极化谱参数影响规律的研究 被引量:1

The Influence of Insulating Oil Aging Degree on Polarization Spectrum in Oil-paper Insulation System of the Transformer
下载PDF
导出
摘要 油浸式电力变压器在运行过程中绝缘油不断地老化,严重影响其运行寿命,因此评估变压器绝缘油老化程度对确保变压器安全可靠运行具有重要意义。基于回复电压的极化谱方法是一种无损的绝缘诊断方法,可以方便地对变压器的绝缘状态进行现场诊断,已经被用来评估变压器的绝缘状态。通过对由三种不同老化程度的绝缘油和普通纤维素绝缘纸组成的绝缘系统进行的回复电压测试,研究了回复电压极化谱在不同老化程度绝缘油下的变化规律。结果表明:绝缘油老化程度对中心时间常数的影响最为明显,对峰值电压和初始斜率的影响则不大,初步建议用中心时间常数来判断绝缘油的老化程度,将峰值电压和初始斜率作为参考。 Insulating oil become an aging in Oil-immersed power transformer while operation, and the operational life will be seriously influenced. Therefore, the assessment of aging degree of insulating oil in transformer makes great sense for the safe and reliable operation of transformer. As a non-destructive insulation diagnostic technique, the polarization spectral method which is based on RVM( recovery voltage measurement) has been employed to assess the state of insulation in transformer. In this paper, RVMs were conducted for the insulating system composed of three types of insulating oil with different aging degrees and kraft paper, and the changing regularities of polarization spectrum based on return volt- age measurement were obtained. The result shows that insulating oil aging effecting on the central time constant is most obvious, but not on the initial slope and the peak voltage, so it is suggested preliminarily to use central time constant to diagnose the aging degree of insulating oil, and initial slope and peak voltage as a reference.
出处 《电气开关》 2015年第4期30-33,36,共5页 Electric Switchgear
关键词 绝缘油 极化谱 回复电压 中心时间常数 介电特性 insulating oil polarization spectrum recovery voltage measurement ( RVM ) central time constant dielectric property
  • 相关文献

参考文献12

  • 1钱政,尚勇,杨莉,严璋.电力变压器固体绝缘状况的综合评估模型[J].西安交通大学学报,2000,34(4):5-9. 被引量:15
  • 2KALOCSAL L. Spectrum of Polarization Phenomena of Long Time-con- stant as a Diagnostic Method of Oil-paper Insulation System CJ. Proceeding of the 3rd International Conference on Properties and Application of Dielec- tric Materials. Tokyo, Japan:IEEE Dielectrics and Electrical Insulation Socie- ty and Institute of Electrical Engineers of Japan, 1991:723 -726.
  • 3NEMETI-I E. Measuring Voltage Response:a Non-destructive Diagnos- tic Test Method of HV Insulation [ J ]. IEE Proceeding of Science. Measure- ment and Technology, 1999,146 (5) :249 - 252.
  • 4Tokyo Electric Co. Inc Hitachi,Ltd. A Diagnostic Method Based on RVM (Return Voltage Measurement)for Condenser Bushing with Oil-Paper Insulation Systems [ J ]. Electric Engineering in Japan, 2000,130 ( 1 ) : 21 - 29.
  • 5ASCHENBRENNER V. Using of Parameters of RVM Measurement for Qualitative Appreciation of Power Transformers Insulation States [ C ]. Trans- mission and Distribution Conference and Exhibition. 2002,1829 -1833.
  • 6OMAR HASSANL,HOSSEIN BORSIL,EMST GOCKENBACH,et al. Diagnostic of Insulation Condition of oil Impregnated Paper Insulation System with Return Voltage Measurements[ C]. 2003 Annual Report Conference on Electrical Insulation and Dielectric Phenomena. USA : IEEE Dielectrics and Electrical Insulation Society ,2003,153 - 156.
  • 7李明华,董明,严璋.一种新的绝缘测试方法——回复电压法[J].高电压技术,2002,28(8):43-45. 被引量:58
  • 8张涛,蔡金锭.应用极化谱分析油纸变压器绝缘纸板水分含量的研究[J].电工电能新技术,2009,28(4):46-49. 被引量:19
  • 9中国科学技术信息研究所.2003年版中国科技期刊印证报告[R].北京:中国科学技术信息研究所,2003.
  • 10中国科学技术信息研究所.2002年版中国科技期刊印证报告[R].北京:中国科学技术信息研究所,2002.

二级参考文献38

共引文献175

同被引文献12

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部