期刊文献+

R404A和R407C在水平强化管外的凝结换热实验研究 被引量:4

Experimental Investigation on Condensation Heat Transfer of R404A and R407C outside Horizontal Enhanced Tubes
下载PDF
导出
摘要 实验研究了近共沸制冷工质R404A与非共沸制冷工质R407C在水平强化换热管管外的凝结换热性能。采用"Wilson图解法"对实验数据进行处理。结果表明:对于R404A和R407C,强化管外的凝结换热系数随着壁面过冷度的增加而增大,呈现出与纯工质冷凝时不同的变化趋势,这主要是近共沸或非共沸工质凝结过程中,某些组分的凝结会遇到其它组分的凝结气膜热阻所造成的;随着过冷度增加,易挥发组分开始凝结,气膜变薄,冷凝传热系数增大。R407C在强化换热管管外的凝结换热系数比R404A要小70%左右,这是由于R407C的温度滑移较R404A要大,管外形成的凝结扩散气膜造成的影响更大。R407C在高热流密度工况下的换热效果提升明显,故应尽量工作在高热流密度区域。 The condensation heat transfer performance outside horizontal enhanced tubes of near-azeotropic refrigerant R404A and zeotropic refrigerant R407 C was investigated in this study. The experimental data were analyzed using Wilson graphical method. The results show that the coefficients of condensation heat transfer outside horizontal enhanced tubes of R404A and R407C increase with the increase of supercooling degree of tube wall, which is different from pure refrigerant. For near-azeotropic or zeotropic refrigerant, some components will encounter the gas film resistance caused by the condensation of other components. With the increase of super- cooling degree of tube wall, the volatile components begin to condense and the gas film becomes thin, thus the coefficient of conden- sation heat transfer will increase. The coefficient of condensation heat transfer outside horizontal enhanced tubes of R407C is 70% lower than R404A, which is due to the fact that the temperature glide of R407C is larger than R404A, and the impact of gas film outside tubes is greater. The heat transfer coefficient of R407C is improved obviously at higer heat flux condition, which is suitable for practical application.
出处 《制冷学报》 CAS CSCD 北大核心 2015年第4期72-77,共6页 Journal of Refrigeration
关键词 强化传热 凝结换热 R404A R407C enhanced heat transfer condensation heat transfer R404A R407C
  • 相关文献

参考文献17

  • 1Cavallini A. Working fluids for mechanical refrigeration [ J]. International Journal of Refrigeration, 1996,19 ( 8 ) : 485-496.
  • 2Chen J, Kiuse H. Concentration shift simulation the mixed re- frigerants R404A, R32,/ R134a and R407C in an air condi- tioning system [ J]. International Journal of HVAC&R Re- search, 1997, 3 (2):149-157.
  • 3刘一民,胡丽英,巢龙兆.混合工质R407C的实验研究[J].流体机械,2003,31(z1):114-116. 被引量:1
  • 4陈九法.关于R407C用于替代R22的研究[J].流体机械,2004,32(8):69-72. 被引量:8
  • 5陈斌,陈光明.R407C、R410A制冷系统相关特性研究进展[J].流体机械,2003,31(2):42-45. 被引量:17
  • 6Boissieux X, Heikal, Johns R A. Two-phase heat transfer coefficients of three HFC refrigerants inside a horizontal smooth tube part : condensation [ J ]. International Journal of Refrigeration, 2000, 23 (5) :345-352.
  • 7南晓红,罗昕岚,C.A.Infante Ferreira.R404A在水平内螺纹管中的冷凝传热研究[J].化学工程,2008,36(5):16-19. 被引量:3
  • 8Cavallini A, Delcol D, Doretti L, et al. Heat transfer and pressure drop during condensation of refrigeration inside horizontal enhanced tubes [ J ]. International Journal of Re- frigeration, 2000, 23 ( 1 ) :4-25.
  • 9成昌锐,王秋旺,刘星,陶文铨.R407C在水平单管外凝结换热的实验研究[J].工程热物理学报,2001,22(S1):50-52. 被引量:10
  • 10Jung D, Kim C B, Hwang S M, et al. Condensation heat transfer coefficients of R22, R407C, and R410A on a hori- zontal plain, low fin, and turbo-C tubes [ J ]. International Journal of Refrigeration, 2003, 26(4) :485-491.

二级参考文献20

  • 1吴华根,束鹏程,邢子文.采用替代工质的空气源热泵性能试验研究[J].暖通空调,2006,36(1):60-62. 被引量:11
  • 2[4]Refrigeration and Air-Condition Technologe [M]. Solkane Pocket Manual.
  • 3[7]Adriana Greco, Rita Mastrullo, Adolfo Palombo. R407C as An Alternative to R22 in Vapor Compression Plant: An Experiment Study[J] .Int. J. of Energy Research, 1997,21:1087 ~ 1098.
  • 4[8]Honeywell Company. Genetron R407C Production rochure.
  • 5Ploecker U, Knapp H, Prausniz J. Calculation of HighPressure Vapor-Liquid Equilibria From a CorrespondingState Correlation with Emphasis on Asynnetric Mixtures[J]. Ind Eng Chem Process Des, 1978,17(3).
  • 6Chen J, Kruse H. Concentration Shift Simulation for the Mixed Refrigerants R404A, R32/R134a and R407C in an Air Conditioning System[J]. Int J of HVAC&R Research,1997,3(2): 149-157.
  • 7Chen J, Kruse H. Calculating Circulation Concentration of Zeotropic Refrigerant Mixtures[J]. Int J of HVAC&R Research, 1995,1(3) :219-231.
  • 8Lee D-Y,et al. Experimental investigation on the drop-in performance of R407C as a substitute for R22 in a screw chiller with shell-and-tube heat exchangers[J]. International Journal of Refrigeration, 2002,25: 575-585.
  • 9Ge Y T, Cropper R. Performance evaluations of aircooled condensers using pure and mixture refrigerants by four-section lumped modelling methods [ J ]. Applied Thermal Engineering ;2005,25 (10):1 549--1 564.
  • 10Boissieux X, Heikal, Johns R A. Two-phase heat transfer coefficients of three HFC refrigerants inside a horizontal smooth tube part Ⅱ: Condensation[ J]. Int J of Refrigeration, 2000,23 ( 5 ):345 --352.