期刊文献+

压差控制下的空调水系统末端流量变化特性 被引量:1

Variation characteristics of air-conditioning water system terminal's flow under pressure difference control
下载PDF
导出
摘要 介绍压差控制下的中央空调水系统在部分负荷时末端支路存在过流、欠流现象,通过计算分析过流、欠流在末端支路上的变化趋势,指出通过改变压差控制点位置或降低空调水系统主干管的阻力损失占比可缓解末端支路的过流和欠流。 The overcurrent and undercurrent phenomenon of terminal branch of central airconditioning water system with part load under pressure difference control are introduced,and their variation tendencies are analyzed by calculation.It is pointed out that the overcurrent and undercurrent phenomenon can be relieved by moving control point of pressure difference or reducing resistance loss ratio of air-conditioning water system's main pipe.
作者 陈文辉
出处 《制冷与空调》 2015年第7期50-53,共4页 Refrigeration and Air-Conditioning
关键词 空调 水力平衡 变流量一级泵 压差控制 阻力损失 air-conditioning hydraulic balance flow-variable primary pump pressure difference control resistance loss
  • 相关文献

参考文献3

二级参考文献5

  • 1陆耀庆.实用供热空调设计手册[M]2版.北京:中国建筑工业出版社,2008.
  • 2GB50736---2012民用建筑供暖通风与空气调节设计规范[s].
  • 3Roy Ahlgren.ITT小红学校中文版——水系统经典书籍[M/OL].[2013-12-26].http:∥www.doc88.com/p-907591399974.html.
  • 4GB 50736—2012民用建筑供暖通风与空气调节设计规范[S].
  • 5陈定艺,刘金祥,徐稳龙,陈晓春,李宁,李澎.部分负荷下二次泵水系统管网特性研究[J].暖通空调,2011,41(11):101-106. 被引量:8