期刊文献+

考虑电网阻抗影响的LCL型并网逆变器控制策略 被引量:11

CONTROLLER DESIGN OF THREE-PHASE INVERTER WITH LCL FILTER CONSIDERING THE GRID IMPEDANCE
下载PDF
导出
摘要 在考虑电网阻抗情况下对带LCL滤波器的三相光伏逆变器稳定性以及相应的控制策略进行研究。详细分析电网阻抗对并网光伏系统稳定性的影响,同时提出基于状态反馈极点配置的逆变器控制策略以实现系统极点的任意配置,从而抑制电网阻抗对系统电能质量以及稳定性的影响。最后建立系统仿真和实验模型进行验证。结果表明:电网阻抗易导致采用PR+HC控制器的光伏并网系统出现不稳定,降低系统并网电能质量;所提出的极点配置方法可有效抑制电网阻抗对系统稳定性影响。 The stability of the three-phase PV inverter with LCL filter and corresponding control strategy were researched considering the grid impedance. First, the grid-connected PV inverter stability was analyzed of grid impedance. Then the inverter control strategy was proposed based on state feedback to achieve the system poles assignment thereby inhibiting the effect on the system power quality and stability considering the grid impedance. Finally the study was validated through simulation. Studies have shown that: the grid impedance can decrease the LCL filter resonance frequency and the PV system with PR+HC controller becomes unstable, severely reducing the power quality; the proposed pole-assignment control strategy can effectively inhibit the grid impedance impact on system stability.
出处 《太阳能学报》 EI CAS CSCD 北大核心 2015年第9期2146-2151,共6页 Acta Energiae Solaris Sinica
基金 国家自然科学基金(51477021) 国家高技术研究发展(863)计划(2011AA05A301)
关键词 光伏逆变器 LCL滤波器 电网阻抗 稳定性 极点配置 PV inverter LCL filter grid impedance stability pole assignment
  • 相关文献

参考文献13

  • 1杜春水,张承慧,刘鑫正,陈阿莲.带有源电力滤波功能的三相光伏并网发电系统控制策略[J].电工技术学报,2010,25(9):163-169. 被引量:32
  • 2刘飞,查晓明,周彦,殷进军,段善旭.基于极点配置与重复控制相结合的三相光伏发电系统的并网策略[J].电工技术学报,2008,23(12):130-136. 被引量:37
  • 3彭双剑,罗安,荣飞,吴敬兵,吕文坤.LCL滤波器的单相光伏并网控制策略[J].中国电机工程学报,2011,31(21):17-24. 被引量:46
  • 4许津铭,谢少军,肖华锋.LCL滤波器有源阻尼控制机制研究[J].中国电机工程学报,2012,32(9):27-33. 被引量:151
  • 5Mao Xiaolin, Raja A. An adaptive controller for inverter-interfaced DGs connected to grids with a wide range ofunknown impedances [A]. 2010 IEEE on EnergyConversion Congress and Exposition (ECCE) [C],Atlanta, USA, 2871-2877.
  • 6Hong S G,Matthew A, Bashar Z. The effect of gridoperating conditions on the current controllerperformance of grid connected photovoltaic inverters [A].The 13th European Conference on Power Electronicsand Applications [ C ], Barcelona, Spain, 2009, 1-8.
  • 7Marco L, Remus T, Frede B. Stability of grid-connectedPV inverters with large grid impedance variation [A].2004 IEEE 35th Annual PESC 04[C],Hebei, China,2004, 4773-4779.
  • 8Marco L, Remus T, Frede B. Stability of photovoltaicand wind turbine grid-connected inverters for a large setof grid impedance values [J]. IEEE Transactions onPower Electronics,2006,21 (1): 263-272.
  • 9He Jinwei, Li Yunwei, Dubravko B, et al. Investigationand resonances damping of multiple PV inverters [A].27th Annual IEEE on Applied Power ElectronicsConference and Exposition (APEC) [C],Florida,USA, 2012, 246-253.
  • 10Sun Jian. Impedance-based stability criterion for grid-connected inverters [J]. IEEE Transactions on PowerElectronics, 2011,26(11): 3075-3078.

二级参考文献62

共引文献296

同被引文献82

引证文献11

二级引证文献95