期刊文献+

数据机房服务器排列方式对冷却效果的影响 被引量:4

Influence of Severs' Arrangement on Cooling Effect in Data Center
下载PDF
导出
摘要 对典型数据机房机柜内气流组织情况进行研究。以1U服务器为例,列举了6种常见的服务器排列方式,涵盖了实际生活中大部分情况,并用Phoenics对其气流组织进行数值模拟,探讨不同服务器布局对机柜冷却效果的影响。模拟结果显示了机柜内部气流组织的分布情况,当服务器采用1个或2个一组,并且中间留有空隙,均匀排列的方式,能最大程度地利用冷量,冷却效果更好。 This paper takes a typical data center as the research object, to study the distribution of airflow in the cabinet, by utilizing racks stocked with 1U servers as an example. Six different rack models covering a wide range of server arrangements are presented. Phoenics is used to investigate the airflow distribution, as well as the cooling effects of different servers' layout. The simulation results show the distribution of airfow inside the cabinet, and one server or two servers as a group with void spaces, even arrangement, can make the cooling capacity to a larger extent. Therefore, it gets better performance in cooling efficiency improvement.
机构地区 南京工业大学
出处 《建筑节能》 CAS 2015年第9期81-84,共4页 BUILDING ENERGY EFFICIENCY
关键词 数据机房 服务器布局 数值模拟 气流组织 冷却 data center sever layout numerical modeling airflow distribution cooling
  • 相关文献

参考文献4

  • 1Bash C E,Patel C D,Sharma R K.Efficient thermal management of data centers-Immediate and long-term research needs[J].HVAC and R Research, 2003,9(2):137-152.
  • 2范昕杰,刘金祥,陈晓春,徐稳龙.数据机房冷通道气流组织改善数值模拟研究[J].建筑热能通风空调,2013,32(3):66-70. 被引量:7
  • 3Rajat Ghosh,Vikneshan Sundaralingam,Yogendra Joshi.Effect of rack server population on temperatatures in data centers [C]//13th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems,2012:30-37.
  • 4Zhang X S,Van Gilder J W,Iyengar M,et al.Effect of rack modeling de-tail on the numerical results of a data center test cell [C]//Thermal and Thermomechanieal Phenomena in Electronic Systems,ITHERM 2008,1 lth Intersociety Conference on IEEE,2008:1183-1190.

二级参考文献5

  • 1C D Patel, R Sharma, C E Bash, et al. Thermal considerations in cooling large scale high compute density data centers [A]. In: Proceedings of 2002 Inter Society Conference on Thermal Pheno -mena [C]. 2002.
  • 2K Karki, S Patankar, A Radmehr. Techniques for controlling airflow distribution in raised-floor data centers [J]. Adv. Electronic Packaging, 2003, (2): 621-628.
  • 3R Schmidt, E Cruz. Cluster of high powered racks within a raised floor computer data center: Effect of perforated tile flow distribution on rack inlet air temperatures [J]. J. Electronic Packaging Trans., 2004, 126(4): 510-518.
  • 4S Shrivastava, B Sammakia, R Schmidt, et al. Comparative analy- sis of different data center airflow management configurations [A]. In: Proceedings of the International Electronic Packaging Technical Conference and Exhibition [C]. San Francisco, 2005.
  • 5R R Schmidt, K C Karki, K M Kelkar, et al. Measurements and Predictions of the Flow Distribution through Perforated Tiles in Raised-Floor Data Centers [R]. ASME, 2001.

共引文献6

同被引文献40

引证文献4

二级引证文献5