结合石家庄地铁地下停车场通风空调系统设计,通过对停车库通风、空调、采暖、排烟4个方面的难点问题进行分析,并通过利用工程经验、借鉴规范等方法,提出全面的系统设计解决方案。研究结论:停车库内通风量、排烟量分别按照3 m层高、实际层高,6次/h换气考虑;检修平台考虑局部空调,提高作业人员舒适度;土壤有蓄热效应,按局部考虑采暖即可,不必对停车库内进行大面积采暖。
With regard to the design of ventilation and air conditioning system of Shijiazhuang metro underground parking, this paper proposes an overall system solution after the analysis of such key issues as air conditioning, heating, ventilation and smoke exhaustion with reference to engineering practices and specifications. The results show that ventilation and smoke exhaustion volumes are calculated on the basis of 3m assumed floor height, the actual height and 6 times of ventilation per hour; the maintenance ped partially with air-conditioning for the benefit mulation, local heating is acceptable without the platform is equip ground heat accu of working staff; with the presence of need for the entire parking lot.
出处
《铁道标准设计》
北大核心
2015年第10期148-151,共4页
Railway Standard Design
基金
铁道第三勘察设计院集团有限公司科技开发课题(721430)
关键词
地铁
地下停车场
环控
活塞风
空调系统
Subway
Underground parking lot
Environmental control
Piston wind