摘要 对一起110 k V金属氧化物避雷器(MOA)发热缺陷原因进行深入剖析,结合缺陷避雷器的红外检测图谱和运行电压下交流泄漏电流阻性分量试验结果,推断发热的原因为内部受潮。对该避雷器进行解体检查,发现避雷器中上部阀片受潮导致发热异常,验证了推断。并从订货、选型、运行方面提出预防措施。 The abnormal temperature rise situation of 110 k V MOA is analyzed deeply.Combined with the infrared detection map of defective arrester and the AC leakage current resistive component under the operation voltage,it is suggested that the abnormal temperature rise situation is caused by internal moisture.Then the suggestion is verified by the strip inspection.The conclusion is that the upper valve arrester damp caused abnormal heat.Prevention measures are put forward from the aspect of order,model selection and operation.
作者 于洋 耿宁
出处 《山东电力技术》 2015年第7期75-77,共3页 Shandong Electric Power
关键词 金属氧化物避雷器 发热异常 内部受潮 红外诊断 metal oxide arrester(MOA) abnormal heat internal moisture infrared diagnostic
  • 相关文献

参考文献4

  • 1王辉,何锦强,赵倡皓,廖永力,李锐海,李盛涛.35kV金属氧化物避雷器雷电冲击老化性能的研究[J].电瓷避雷器,2014(4):72-77. 被引量:25
  • 2王树声.国家电网公司生产技能人员职业能力培训专用教材—变电检修[M].北京:中国电力出版社,2011.
  • 3DL/T 664—2008带电设备红外诊断应用规范[S].北京:中国电力出版社,2008.
  • 4Q/GDW 454—2010金属氧化物避雷器状态评价导则[S].北京:中国电力出版社,2010.

二级参考文献1

共引文献24

同被引文献21

引证文献2

二级引证文献2