摘要
发电机是发电厂的三大主机之一,其安全稳定性在电力企业安全生产中至关重要。大型发电机组采用双重化微机保护装置,为机组的安全稳定运行提供保障。本文从某台1000MW燃煤机组的发电机设备发生故障,造成机组全停的事故入手,对继电保护动作的记录及试验结果进行分析,找出故障发生的原因,提出事故处理方案及防范措施,以避免和减少同类故障的发生。
Generator is one of the three core equipment of power plant. It is a primary electrical that can convert me-chanical energy into electrical energy. Large generator equip with Dual-computer protection device. Its safe operation is very important to guarantee the safe and stable operation of power grid. This article firstly discusses an 1000MW generator acci-dent which causing the unit to a full stop, then analyzes the reasons that contributes to the problems focus on the records of the Relay protection action and the experiments’ results. Therefore , this article puts forward the method to deal with the fault is put forward, in order to avoid and reduce the occurrence of the same kind of failure.
关键词
发电机
故障
原因分析
处理
generator power system
electrical failures
reason analysis
practical methods