期刊文献+

闭式冷却塔在石化行业循环水领域的开发与应用 被引量:6

Development and Application of Closed Cooling Towers in the Circulating Water System of Petrochemical Industry
下载PDF
导出
摘要 石化行业现有的开式塔越来越不能满足生产需要,而以闭式冷却塔为核心的闭式循环水技术,其不仅可以保证循环水质,而且还具有节水节能、减少药剂投加、减少二次污染等优点。经过全年的运行成本分析,闭式塔较开式塔可节省水耗达40%以上,节省电耗达20%以上,在现有的石化行业循环水领域具有非常大的应用价值。 The existing opened towers in petrochemical industry can not meet the needs of production, and the closed circulating water technology based on the closed cooling towers, not only can ensure the circulating water quality, but also has the advantages of saving water, saving energy, reducing the dosage and reducing the second pollution. After analysis of the annual operating cost, compared to the opened towers, the closed cooling towers can save water consumption more than 40%, save power consumption more than 20%,so it has very large application value in existing circulating water system of petrochemical industry.
出处 《当代化工》 CAS 2015年第9期2204-2206,共3页 Contemporary Chemical Industry
基金 中国石化集团公司资助项目 项目号:CLY14043
关键词 闭式冷却塔 石化行业 节水 节能 Closed cooling towers Petrochemical industry Saving water Saving energy
  • 相关文献

参考文献7

二级参考文献23

  • 1苏东龙 等.应用蒸发式冷凝器之空调机的运转性能研究[J].冷冻与空调,2001,(10):112-118.
  • 2ASHRAE. Systems and equipment [ M ]. USA : American Society of Heating, Refrigeration and Air Conditioning Engineers, 1992.
  • 3ASHRAE. Fundamentals [ M ]. USA : American Society of Heating, Refrigeration and Air Conditioning Engineers, 1997.
  • 4POPPE M, ROGENER H. Evaporative cooling systems [ M ]. Germany : Section Mh, 1984.
  • 5DREYER A A. Analysis of evaporative coolers and condensers [ D ]. Republic of South Africa: University of Stellenbosch, 1988.
  • 6HEYNS J A, KROGER D G. Experimental investigation into the thermal-flow performance characteristics of an evaporative cooler [ J 1. Applied Thermal Engineering, 2010,30(5) :492-.498.
  • 7HASAN A, SIREN K. Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings [ J ]. Energy and Buildings, 2002, 34 (5) : 477 -486.
  • 8FACAO J, OLIVEIRA A C. Thermal behaviour of closed wet cooling towers for use with chilled ceilings[J]. Applied Thermal Engineering, 2000,20 ( 13 ) : 1225-1236.
  • 9MIZUSHINA T, ITO R, MIYASHITA H. Experimental study of an evaporative cooler [ J ]. International Chemical Engineering, 1967,7 (4) :727-732.
  • 10NIITSU Y, NAITO K, ANZAI T. Studies on characteristics and design procedure of evaporative coolers [ J ]. Journal of SHASE Japan, 1969,43 (7) : 581-590.

共引文献23

同被引文献57

引证文献6

二级引证文献8

相关作者