基于ATP-EMTP的10kV配电线路雷击性能研究 被引量:16

Research on Lightning Performance of 10 kV Distribution Lines Based on ATP-EMTP
原文传递
导出
摘要 针对雷击10 kV架空配电线路时,配电线路直击雷过电压的计算与分析展开了一系列的研究。利用ATP-EMTP软件建立了直击雷过电压仿真模型,对比分析了雷直击杆塔顶部和雷直击相导线两种情况下的直击雷过电压波形和幅值。对10 kV农村架空配电线路遭受高幅值雷电流时的直击雷闪络特性做出了相关计算,给出了遭受高幅值雷电流时的绝缘闪络个数,雷击闪络时的雷电流沿线分布情况。仿真结果表明,雷电流幅值越大,雷击瞬间发生杆塔闪络的范围也在扩大,而且发生闪络的杆塔入地电流沿雷击点向两边递减。 In case of the lightning strike on 10 kV overhead distribution lines, a series of studies on the calculation and analysis of distribution lines direct lightning overvoltage are carried out. Based on ATP-EMTP software, the simulation model of direct lightning overvoltage is established, and the direct lightning overvoltage waveform and amplitude when lightning strike the top of the tower or strike the lightning conductors. The relevant calculations about flashover performance against direct lightning when the high amplitude lightning current strikes 10kV rural overhead distribution lines are carried out, and the numbers of insulation flashover and the lightning current distributions along the lines when subjected to high magnitude lightning current are provided. The simulation results show that the greater the lightning current amplitude, the range of lightning flashover tower is expanding, and the current into the ground is descending along the lightning point to both sides.
作者 顾用地
出处 《电瓷避雷器》 CAS 北大核心 2015年第5期154-158,共5页 Insulators and Surge Arresters
关键词 10 kV架空配电线路 ATP-EMTP 直击雷过电压 闪络特性 绝缘闪络 10 kV overhead distribution lines ATP-EMTP direct lightning overvohage flashover performance insulation flashover
  • 相关文献

参考文献5

二级参考文献49

  • 1陈伟明.10kV架空绝缘导线雷击断线分析及预防[J].供用电,2005,22(5):48-50. 被引量:40
  • 2周远翔,鲁斌,李震宇,徐旭,胡航海,王宁华,梁曦东,关志成.蒙特卡罗法计算线路雷击跳闸率随机过程研究[J].高电压技术,2007,33(5):1-5. 被引量:39
  • 3Piantini A. Lightning protection of overhead power distribution lines[C]// Proceedings of the 29th International Conference on Lightning Protection, (invited lecture). Uppsala, 2008.
  • 4IEEE Std 1410 IEEE Guide for improving the lightning performance of electric power overhead distribution lines[S], 2004.
  • 5S P da Silva, Piantini A, J L De Franco, et al. Lightning performance studies for a 13.8 kV distribution network[C]// Proceedings of the Ⅶ International Symposium on Lightning Protection. Sao Paulo, 2003:137-143.
  • 6Borghetti A, Nucci C A, Paolone M, et al. Effect ot the lateral distance expression and of the presence of shielding wires on the evaluation of the number of lightning induced voltages[C] // Proceedings of the 25th International Conference on Lightning Protection. Rhodes, 2000: 340-345.
  • 7Paolone M, Nucci C A, Petrache E, et al. Mitigation of lightning induced overvoltages in medium voltage distribution lines by means of periodical grounding of shielding wires and of surge attesters: modeling and experimental validation [J]. IEEE Transactions on Power Delivery, 2004, 19(1): 423-431.
  • 8Yokoyama S. Lightning protection of MV overhead distribution lines[C]// Proceedings of the Ⅶ International Symposium on Lightning Protection. Curitiba, 2003: 485-507.
  • 9Piantini A, Janiszewski J M. Lightning induced voltages on overhead lines: the effect of ground wires[C]// Proceedings of the 22nd International Conference on Lightning Protection. Budapest, 1994:R3b/1 R3b/5.
  • 10Piantini A, Janiszewski J M. The effectiveness of surge arresters on the mitigation of lightning induced voltages on distribution lines[J]. Journal of Lightning Research, 2007, 2: 34-52.

共引文献26

同被引文献135

引证文献16

二级引证文献103

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部