摘要
江南某小城镇污水处理厂采用预处理/初沉消化池/(A/O)生化池/液氯消毒工艺,出水COD≤50 mg/L、BOD_5≤10 mg/L、SS≤10 mg/L、TP≤0.5 mg/L,达到了《城镇污水处理厂污染物排放标准》(GB 18918—2002)的一级A标准。运行表明,该工艺具有基建投资省、运行费用低、操作管理方便、处理效果稳定的特点。
The combined process of pretreatment, primary sedimentation digestion tank, A/O bio- chemical tank and chlorine disinfection is used in the sewage treatment plant in a small town in South of Yangtze River. The concentrations of COD, BOD5, SS and TP in the effluent were equal to or less than 50 rag/L, 10 rag/L, 10 mg/L and 0.5 mg/L respectively, meeting the first class A criteria specified in the Discharge Standard of Pollutants for Municipal Wastewater Treatment Plant (GB 18918 -2002). The combined process has the characteristics of low investment and operation cost, simple operation and management, and stable treatment effect.
出处
《中国给水排水》
CAS
CSCD
北大核心
2015年第20期97-100,共4页
China Water & Wastewater
关键词
小城镇污水
初沉消化池
A/O生化池
small town sewage
primary sedimentation digestion tank
A/O biochemical tank