220kV输电线路雷击双回同跳故障原因分析及解决措施 被引量:2

Lightning Protection Failure Analysis of Double-Circuit Flashover of 220 kV Transmission Line and Its Treatment
下载PDF
导出
摘要 针对包头供电局包青220 kV同塔双回输电线路杆塔发生的2起双回同跳故障,结合故障情况以及线路运行参数对故障原因进行分析,运用EMTP电磁暂态计算软件进行反击故障仿真。仿真结果表明:一定幅值的雷电流击中杆塔顶端时会造成2回线路L3相同跳。通过分析绝缘子串两端雷电过电压中几个分量得知,工频相位角是影响双回输电线路三相闪络顺序的主要原因。对此提出安装线路避雷器以及降低冲击接地电阻等措施以提高线路的耐雷水平。 Double-circuit flashover occured twice on Baoqing 220 kV double-circuit towers.The causes of failure was analyzed according to the accident and the operation parameters,with EMTP electromagnetic transient calculation software to simulate the accidents.According to the results,double-circuit three-phase flashover could be caused by the lightning current hiting the tower top.The analysis of insulator string voltage showed that the power frequency voltages influenced largely flashover phase sequence.Line arrester installation and the impulse grounding resistance reduction was proposed to improve the lightning withstand level.
机构地区 包头供电局
出处 《内蒙古电力技术》 2015年第5期30-34,共5页 Inner Mongolia Electric Power
基金 内蒙古电力(集团)有限责任公司2014年第一批科技项目(510112140006)
关键词 220 KV输电线路 同塔双回线路 双回同跳故障 EMTP 耐雷水平 工频电压 220 kV transmission lines double-circuit transmission line double-circuit flashover EMTP lightning withstand level power frequency voltage