期刊文献+

HM-JD-L28型新型石墨复合接地体与常规降阻方式降阻效果的对比分析 被引量:9

Comparative Analysis of HM-JD-L28 Composited Grounding Conductor and Routine Grounding Resistance Reducing Measure
原文传递
导出
摘要 输电线路杆塔接地对电力系统的安全稳定运行至关重要,降低杆塔接地电阻是提高线路耐雷水平,减少线路雷击跳闸率的主要措施。介绍了HM-JD-L28型新型石墨复合接地体的性能特点并将其与常规降阻方式如:接地模块、降阻剂、增加射线长度等在不同情况下的降阻效果进行了分析对比,对如何使用接地模块、降阻剂提出了意见:不推荐在土壤电阻率低于500Ωm的地区使用接地模块及降阻剂,降阻效果不明显。 The grounding system of transmission lines tower play an important role for the stability of the power grid, the main measure to improve lightning withstand level and reduce lightning trip-out rate is reducing grounding resistance. The characteristic of HM-JD-L28 composited grounding conductor is introduced, and several common grounding grounding module, resistance reducing agent and resistance reducing measures such as: increasing the length of grounding conductor are analyzed and compared, suggestions about the usage and effect of grounding module and resistance reducing agent are proposed: using grounding module and resistance reducing agent in the soil where resistivity is lower than 500 Ωm is not recommended, because the resistance reducing effect is not obvious.
作者 龚若涵
出处 《电瓷避雷器》 CAS 北大核心 2015年第6期69-72,79,共5页 Insulators and Surge Arresters
关键词 HM-JD-L28型新型石墨复合接地体 降阻剂 接地模块 工频接地电阻 降阻效果 HM-JD-L28 new graphite composite grounding conductor resistance reducing agent grounding module power frequency grounding resistance resistance reducing effect
  • 相关文献

参考文献14

二级参考文献60

共引文献100

同被引文献115

引证文献9

二级引证文献34

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部