摘要
从抑制结霜的角度出发,提出了该系统。分析了室外空气温度、相对湿度对系统性能的影响,并与采用电加湿的传统空气源热泵系统进行了对比。结果表明:室外空气相对湿度为79%时,随着室外空气温度从-4℃升高到5℃,系统性能系数COPs从2.2升高到4.1,与采用电加湿的传统空气源热泵相比,COIPs可提高24%~41%;相对湿度对COPs的影响不大,相对湿度在一定范围内增大时,COPs会略有增加;与传统空气源热泵相比,该系统在冬季湿冷地区应用具有较大的节能潜力。
From the perspective of preventing frosting, proposes a frost-free air-source heat pump (FFASHP) system using liquid desiccant. Investigates the effects of the outdoor air temperature and relative humidity(RH) on the performance of the system. Compares the performance of the FFASHP system with the conventional air-source heat pump (ASHP) system using electric humidification. The results show that when the outdoor air RH is 79%, with the outdoor air temperature increasing from - 4 ℃ to 5 ℃, COPs of the system increases from 2.2 to 4.1, which is 24% - 41% higher than that of the conventional ASHP system using electric humidification. The COP~ increases slightly with the outdoor air RH in a certain range. Compared with the conventional ASHP system, the FFASHP system will be more efficient in cold-moist regions in winter.
出处
《暖通空调》
北大核心
2015年第12期82-87,共6页
Heating Ventilating & Air Conditioning
基金
江苏省自然科学基金项目"蓄能型太阳能振荡热管热泵系统热力性能及动态特性研究"(编号:BK20151549)
"一种冷凝热分段利用的热湿独立处理空调系统构建与研究"(编号:BK2011791)
关键词
无霜型空气源热泵
溶液
除湿
再生
模型
性能系数
frost-free air-source heat pump, solution, dehumidification, regeneration, model, COP