期刊文献+

电网电压不平衡时DFIG网侧变流器新型双环控制策略 被引量:10

New Double-Loop Control Strategy for DFIG Grid-Side Converter Under Unbalanced Grid Voltage
下载PDF
导出
摘要 电网电压不平衡时,电网电压出现的负序电压会对双馈风力发电机的正常运行产生很大的影响,甚至损坏发电机组。通过对双馈异步风力发电机网侧变流器的模型进行推导和分析,提出了一种双馈风力发电机网侧变流器在电网不平衡条件下改进的双环控制策略。该策略的外环采用模糊PID控制,而内环采用谐振PR控制,从而通过同时控制正、负序可以消除直流侧二次谐波,得到恒定的直流电压。最后,利用MATLAB/Simulink对该策略进行了试验验证,仿真结果证明了该策略的正确性和有效性。 When the grid voltage unbalance,the grid voltage negative sequence will produce and it will bring great influence on DFIG or even damage the generators. The grid-side converter model doubly fed induction generator was derived and analyzed, a improved control strategy for double-fed wind turbine grid-side converter under unbalanced grid voltage was presented. The control strategy using fuzzy PID for outer loop and resonant control for inner,by simultaneously controlling the positive and negative sequence the second harmonic could be eliminated and finally get a constant DC voltage. Finally,the use of MATLAB / Simulink experimentally validated control strategy and simulation results showed the correctness and effectiveness of the control strategy.
出处 《电机与控制应用》 北大核心 2015年第12期35-42,共8页 Electric machines & control application
基金 国家自然科学基金项目(61304134) 上海市重点科技攻关计划(14110500700) 上海市电站自动化技术重点实验室基金项目(13DZ2273800) 上海市自然科学基金项目(13ZR1417800)
关键词 电网电压不平衡 双馈异步风力发电机 网侧变流器 模糊PID 比例谐振 grid voltage unbalance doubly-fed induction generator(DFIG) grid-side converter(GSC) fuzzy PID proportion resonance(PR)
  • 相关文献

参考文献13

二级参考文献125

共引文献315

同被引文献91

  • 1程鹏,马静,李庆,王伟胜.风电机组电网友好型控制技术要点及展望[J].中国电机工程学报,2020,40(2):456-467. 被引量:29
  • 2唐冰婕,迟永宁,田新首,李琰.基于阻抗模型闭环极点的双馈风电系统次同步振荡稳定性分析[J].电网技术,2020,44(3):871-880. 被引量:28
  • 3CHENGKWE, LIN J K, BAO Y J, et al. Review of the wind energy generating system [ C ]//8th International Conference on Advances in Power System Control, Operation and Management, Hong Kong, China, 2009: 1-7.
  • 4FREDE B, KE M. Future on power electronics for wind turbine systems[ J]. IEEE Journal of Emerging and Selected Topics in Power Electronics, 2013,3 ( 1 ) : 139-152.
  • 5MARCO L, ROBERTO C, MARTA M, et al. Overview of muhi-MW wind turbines and wind parks[J].IEEE Transactions on Industrial Electronics, 2011,58(4) : 1081-1095.
  • 6YUAN X B. Multilevel modular high power converters for 10 MW wind turbines [ C] // IEEE International Symposium on Industrial Electronics, Taipei, Taiwan, 2013 : 1-7.
  • 7MA K, BLAABJERG F. Multilevel converters for 10MW wind turbines [ C ] // in Proc EPE, Birmingham, UK, 2011: 1-10.
  • 8TAPIA A, TAPIA G, OSTOLAZA J, et al. Modeling and control of a wind turbine driven doubly fed induction generator[J]. IEEE Transactions on Energy Conversions, 2003,18 ( 2 ) : 193-204.
  • 9YOUNG K. D, UTKIN V l, OZGUNER U . A control engineer's guide to sliding mode control [ J ]. IEEE Transactions on Control System Technolgy, 1999,7( 3 ) : 328-342.
  • 10UTKIN V I. Sliding mode control design principles and applications to electric drives[J]. IEEE Transactions on Industrial Electronics, 1993,40( 1 ) : 23-36.