摘要 针对不同间歇使用模式下的建筑,对其使用期室外间断性逐时温度进行统计分析,提出间歇运行建筑采暖室外计算温度的统计方法。选取各气候区典型城市进行取值分析,结果表明:对于短期间歇运行建筑,在严寒、寒冷A区和寒冷B区分别可提高现行规范值5.3℃、4.6℃和1.6℃;对于长期间歇运行建筑,在严寒、寒冷A区和寒冷B区分别可提高现行规范值7.4℃、5.3℃和4.4℃。 This paper aimed at different intermittent mode of building, analyze the discontinuity outdoor temperature in usage period, put forward the methods of the heating outdoor design temperature for intermittent operation building, select some typical cities in different climate zones to analysis. The results show that: for short-term intermittent operation construction, in the cold area, cold A area and cold B area, respectively, the statistics is higher than standard value of 5.3℃, 4.6℃ and 4.6℃; for long-term intermittent operation construction, in the cold area, cold A area and cold B area, respectively, the statistics is higher than standard value of 7.4℃, 5.3℃ and 5.3℃.
出处 《建筑热能通风空调》 2015年第6期11-14,共4页 Building Energy & Environment
基金 国家自然科学基金(No.51408462) 陕西省教育厅专项基金(2013JK0985) 教育部博士点基金(20136120120003)
关键词 间歇运行 采暖室外计算温度 间断性气象数据 intermittent operation, the heating outdoor design temperature, intermittent meteorological data