白天鹅宾馆末端压差式空调冷冻水的平衡

AC Chilled Water Balance by Terminal Pressure difference of White Swan Hotel
下载PDF
导出
摘要 通过广州沙面白天鹅宾馆机械压差式空调冷冻水的水力平衡的调试描述,说明此类空调工程冷冻水流量的设计特点与调试难点。通过阀门操作试验、系统扬程检测、需求流量校核、划分调试模块、现场压差测量等对冷冻水作使用平衡;对问题作技术分析,采取管路清理与降低水阻等办法处理。现代高级酒店空调建筑较多,此文对此类空调的水量平衡调试有一定的参考作用。 Through a description of Guangzhou Shamian Island White Swan Hotel's mechanical differential pressure type air conditioning chilled water hydraulic balance debugging,indicating that this kind of air conditioning chilled water flow design features and debugging difficulty. Through the valve operation test,system head detection,traffic demand check,adjustable module is divided,field differential pressure measurement to balance chilled water; take pipeline cleaning and reduce water barrier approach to the problem. Modern advanced hotel air conditioning building is more,this paper has a reference in the adjustment of the water balance of the chilled water.
出处 《制冷》 2015年第4期65-70,共6页 Refrigeration
关键词 静态平衡阀 机械压差式平衡阀 流量与特性 设计修改流量 划分调试模块 流量偏差 最不利环路 压差芯轴调整 Static balance valve Mechanical differential pressure balance valve Flow and characteristic Design change flow Dividing the debug module Flow deviation The most unfavorable loop Pressure difference core shaft