期刊文献+

室外照明配电接地类型20m距离规定的探讨

Discussion of 20 m Provision of Grounding Mode For Outdoor Lighting Distribution System
下载PDF
导出
摘要 计算了建筑物内发生高、低压接地故障时对邻近建筑的室外人员、照明设备以及室外照明保护电器动作可靠性的影响。指出采用降低配电系统的接地电阻和室外照明灯具的保护接地电阻,以及选用合适的保护电器参数等措施,可以在邻近建筑物的室外照明配电系统中采用TT接地类型。 This paper calculated the influencing on outdoor people and hghting appliances, and the operating time of protective device for outdoor lighting appliance while the high and low voltage grounding faults occurred in building. It is pointed out that by u,*ing of lower grounding resistance of distribution system, protecting grounding resistance of outdoor lighting appliance, and proper choice of protective device, TT system can be applied in outdoor lighting distribution system near buildings.
作者 谭激
出处 《现代建筑电气》 2015年第12期15-20,共6页 Modern Architecture Electric
关键词 TT系统 室外地面电位 预期接触电压 屏蔽效应 互电阻 动作时间 TT system outdoor ground potential prospective touch voltage shielding effect mutual resistance operating time
  • 相关文献

参考文献2

  • 1GB/T50065-2011.交流电气装置的接地设计规范[S].
  • 2川濑太郎.接地技术与接地系统[M].北京:科学出版社,2001.8.

共引文献32

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部