摘要
针对柬埔寨达岱水电站主变压器低压侧区外一起差动保护误动故障,通过对变压器保护装置上的主变参数、CT变比,尤其是变压器的绕组组别进行分析,结果表明,主变低压侧区外差动保护误动作是因主变绕组组别整定错误造成的,经处理后,主变恢复正常运行。
In the Tatay Hydropower Station of Cambodia , an external differential protection mis-operation is observed in the low voltage side of the main transformer .With a detailed analysis on the main transformer parameters of the protec-tion device, the current transformer (CT) ratio, and especially the winding groups of the transformer , it shows that this fault could be caused by the wrong setting of the winding groups .Treatment measures are then carried out corresponding-ly.After the treatment , the main transformer operates well .
出处
《水电与新能源》
2015年第12期52-56,共5页
Hydropower and New Energy
关键词
绕组组别
相间短路
相位校正
主变差动保护
winding group
interphase short circuit
phase correction
main transformer differential protection