摘要
介绍高压隔离开关过热缺陷的判断依据,以及河北省南部电网高压隔离开关的过热缺陷情况,分析缺陷发生的原因,认为其主要原因是老旧隔离开关设计结构不合理、元件质量不良、现场安装工艺不良和运行维护不当,提出隔离开关过热缺陷的反事故措施。
According to overheating defects of high-voltage disconnecting switch,the causes for defects have been analyzed,and the main reason is that the design structure not reasonable of old disconnecting switch,the bad component quality,the badly spot install craft and the not appropriate of maintenance.Combined with application in the Hebei south network of disconnecting switch,the analysis of typical defects and the processing methods have been discussed,and the preventive measures have been proposed.
出处
《河北电力技术》
2015年第5期46-49,共4页
Hebei Electric Power
关键词
高压隔离开关
过热缺陷
防范措施
high-voltage disconnecting switch
overheating defects
preventive measures