期刊文献+

Experimental Study on Rack Cooling System based on a Pulsating Heat Pipe 被引量:3

Experimental Study on Rack Cooling System based on a Pulsating Heat Pipe
原文传递
导出
摘要 A rack cooling system based on a large scale flat plate pulsating heat pipe is proposed. The heat generated from IT equipment in a closed rack is transferred by the rear door pulsating heat pipe to the chilled air passage and is avoided to release into the room. The influence of the start-up performance of the heat pipe, the load of the rack and the load dissipation to the temperature and the velocity distribution in the rack are discussed. It is found that the temperature would be lower and the temperature distribution would be more uniform in the rack when the pulsating heat pipe is in operation. Also, the effect of rack electricity load on temperature distribution is analyzed. It is indicated that higher velocity of chilled air will improve heat transfer of the rack.
作者 LU Qianyi JIA Li
出处 《Journal of Thermal Science》 SCIE EI CAS CSCD 2016年第1期60-67,共8页 热科学学报(英文版)
基金 supported by National Natural Science Foundation of China(No.51376019)
关键词 cooling rack data center pulsating heat pipe 脉动热管 冷却系统 机架 温度分布 试验 速度分布 冷却空气 启动性能
  • 相关文献

参考文献17

  • 1Ebrahimi K., Jones G E, and Fleischer A. S., (2014), A Review of Data Center Cooling Technology, Operating Conditions and the Corresponding Low-grade Waste Heat Recovery Opportunities, Renewable & Sustainable Ener- gy Reviews, Vol. 31, No. 2, pp. 622-638.
  • 2Belady C., Rawson A., Pfleuger J., et al, (2008), Green Grid Data Center Power Efficiency Metrics: PUE and DCIE, White paper 6, Green Grid.
  • 3Pelley S., Meisner D., Wenisch T. E, and VanGilder J. W., (2009), Understanding and Abslraeting Total Data Center Power, Workshop on Energy-Efficient Design in Interna- tional Symposium on Computer Architecture (ISCA-36), Austin, Texas, June 20, pp. 1-6.
  • 4Dunlap K., Rasmussen N., (2014), Choosing Between Room, Row, and Rack-based Cooling for Data Centers, White paper 130, Schneider Electric.
  • 5Rambo J. D., Joshi Y. K., (2003), Multi-scale Modeling of High Power Density Data Centers, ASME 2003 Inter- national Electronic Packaging Technical Conference and Exhibition, American Society of Mechanical Engineers, Maul, July 6-11, pp. 521-527.
  • 6Ouchi M., Abe Y., Fukagaya M., et al., (2012), New Thermal Management Systems for Data Centers, Journal of Thermal Science and Engineering Applications, Vol. 4, No. 3, 031005.
  • 7Yu C., Yuzhun E, and Yonglin J., (2011), Design and Si- mulation of the Evaporator for Cooling System of the Blade Server, Measuring Technology and Mechatronics Automation (ICMTMA), 2011 Third International Con- ference, IEEE, Shanghai, China, January 6-7, VoL 1, pp. 922-925.
  • 8IBM test labs, (2005), IBM Rear Door Heat Exchanger, Technical report 04-05, IBM Knowledge Center.
  • 9Ellsworth M. J., Campbell L. A., Simons R. E., et al., (2008), The Evolution of Water Cooling for IBM Large Server Systems: Back to the Future, Thermal and Ther- momechanical Phenomena in Electronic Systems, ITHERM 2008, llth Intersociety Conference, IEEE, Or- lando, FL, USA, May 28-31, pp. 266-274.
  • 10Hewlett-Packard Development Company, (2007), HP Mo- dular Cooling System: water cooling technology for high- density server installations, Technical report TC070407TB, Hewlett-Packard Development Company, L.P., Houston, USA.