500kV GIS变电站VFTO对于电子式互感器的电磁骚扰研究 被引量:37

Study on the Impact of VFTO Electromagnetic Interference on Electronic Transformers in 500 kV GIS Substation
下载PDF
导出
摘要 随着气体绝缘全封闭组合电器(GIS)的广泛使用,由隔离开关和断路器操作引起的快速暂态过电压(VFTO)带来的危害越加明显。以某典型500 kV GIS智能变电站为计算原型,研究500 kV GIS变电站VFTO对电子式互感器的电磁骚扰。以噪声源和传播路径为基础,通过建立噪声耦合近似模型,实现对电子式互感器干扰信息的定性分析研究。通过分析发现,互感器耦合路径上的耦合电容C_L和C_N越小,VFTO噪声耦合效率越低,VFTO对电子式互感器的噪声影响也越小。研究结果表明,低频段通过修正C_L和C_N实现对电磁干扰的抑制,高频段采用滤波和屏蔽最为有效。通过现场实测证实,未安装防护装置情况下,测得数字采集卡输入端耦合VFTO最高幅值达到9.9 kV,采用电磁兼容综合防护措施后,VFTO最高幅值为0.61 V。 With the widespread use of the gas insulated switchgear( GIS),the harm of very fast transient overvoltage( VFTO) caused by the disconnecting switch( DS) and the circuit breaker( CB) operation becomes increasingly obvious. One 500 k V GIS smart substation is used as a prototype to study the impact of VFTO electromagnetic interference on electronic transformers in 500 k V GIS substation. Base on the noise source and the transmission pathway,a noise coupling model has been set up in order to analyze the VFTO electromagnetic interference on electronic transformers qualitatively. It has been found that the decrease of the coupling capacity of transformer,i. e. CL,and CN,will contribute to the low noise coupling effect of VFTO. The conclusion shows that the most effective method for interference reduction is to revise CL,CNin the low frequency and add low band filter and shielding box in the high frequency. It has been proved by experimental data that the VFTO maximum amplitude is reduced from 9. 9 k V to 0. 61 V by using this method.
出处 《电工技术学报》 EI CSCD 北大核心 2016年第1期85-90,共6页 Transactions of China Electrotechnical Society
关键词 VFTO 电子式互感器 噪声耦合模型 干扰抑制 Very fast transient overvoltage electronic transformer noise coupling model interference reduction
  • 相关文献

参考文献16

  • 1Fujimoto N.Mechanism and analysis of short raise-time GIS transients[C]//CIGRE Symposium,Vienna,Aastria,1987:5-7.
  • 2张重远,梁贵书,崔翔,吴茂林.GIS隔离开关操作对二次设备的影响[J].高电压技术,2002,28(2):5-7. 被引量:53
  • 3张重远,梁贵书,崔翔.气体绝缘变电站内电压互感器高频传输函数模型的建立[J].电工技术杂志,2002,24(12):26-28. 被引量:7
  • 4Fujimoto N,Dick E P,Bosggs S A,et al.Transient ground potential rises in Gas insulated substations-experimental studies[J].IEEE Transactions on Power Apparatusand System,1982,101(11):3603-3609.
  • 5Dick E P,Fujimoto N,Ford G L,et a1.Transient ground potential rises in gas insulated substations-problem identification and mitigation[J].IEEE Transactions on Power Apparatus and System,1982,101(11):3610-3619.
  • 6Haznadar Z,Carsimamovic S,Mahmutcehajic R.More accurate modeling of gas insulated substation components in digital simulations of very fast electromagnetic transients[J].IEEE Transactions on Power Delivery,1992,7(1):434-441.
  • 7Nitzschke D,Bauer H.Simulation of transient disturbance voltages in substations using a combination of MoM and TLT[C]//EMC Zurich 2001 Symposium,Zurich,Switzerland,2001.
  • 8Gustavsen B,Semlyen A.Rational approximation of frequency domain Responses by vector fitting[J].IEEE Transactions on Power Delivery,1999,l4(7):1052-1061.
  • 9Heimbach M.VFT studies on current and voltage transformersin GIS by means of all iterative pole-zero-removal method for simulating the transfer function[C]//9th International Graz,Symposium on High Voltage Engineering,Graz,Austria,1995.
  • 10Zhang Zhongyuan,Liang Guishu,Cui Xiang,et a1.A high frequency transfer function model of potential transformer in GIS[C]//2002 3rd International Symposium on Electromagnetic Compatibility,Beijing,2002.

二级参考文献108

共引文献258

同被引文献379

引证文献37

二级引证文献213

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部